Plan Review Notes
Plan Review Notes For Permit 03110607
Permit Number 03110607
Review Stop E
Sequence Number 4
Notes
Date Text
2004-12-28 00:00:00*********** UNSAT 3RD REVIEW **********
  
 **** PLEASE SEE NOTES #'S 3 AND 4 FROM
 PREVIOUS REVIEW ARE STILL THE SAME.
 PLEASE SEE ATTACHED PREVIOUS COMMENTS.
  
 1)NOTE: PLEASE SEE 250.6,250.24, THERE
 IS NO EQUIPMENT GROUNDING CONDUCTOR
 FROM
 METER TO MAIN(FIRST MEANS OF DISC).
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH FEEDER SCHEDULE ON PANEL
 SCHEDULES.
 215.5
  
 *** NEW NOTE***
  
 1)NOTE: PLEASE SEE PLANS ARE NOW
 SIGNED,
 DATED AND SEALED BY AN ENGINEER AS
 BEING
 RESPONSIBLE FOR PLANS.
 PLEASE SEE FAC 61G15-23.002, A TITLE
 BLOCK IS REQUIRED ON PLANS WITH
 INFORMATION AS SETFORTH IN FAC/ FS.
  
 PLEASE SEE ATACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL
 WITH REPEAT COMMENTS.
 THIS IS GIVEN ONLY AS A NOTICE AT THIS
 TIME.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS FOR REVIEW AND STAMPING.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]