Plan Review Notes
Plan Review Notes For Permit 03110607
Permit Number 03110607
Review Stop E
Sequence Number 3
Notes
Date Text
2004-11-30 00:00:00*********** UNSAT ********
  
 1)NOTE: PLEASE SEE # OF CONDUCTORS
 INDICATED ON RISER FROM METER TO MAIN.
 THIS IS A 3-PHASE SERVICE, YET ONLY
 SHOWS 3-CONDUCTORS.
  
 2)NOTE: PLEASE ALSO SEE #OF CONDUCTORS
 SHOWN IN A SINGLE 2" CONDUIT. PLEASE
 SEE
 TABLES IN CHAPTER 9 NEC FOR CONDUIT
 FILL.
  
 3)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW SHOWN FROM
 METER TO MAIN. AN EQUIPMENT GRND IS NOT
 INSTALLED FROM METER TO THE FIRST MEANS
 OF DISCONNECT. 250.6,250.24.
  
 4)NOTE: PLEASE CORRELATE RISER WITH
 PANEL "A" FEEDER SCHEDULE, AS ON NOTES
 ABOVE.
  
 5)NOTE: PLEASE SEE RE-SUB SHEET
 MENTIONS
 PERMIT APPLIACTION TO BE BROUGHT IN BY
 THE 11/24. THIS IS REQUIRED WHEN
 RE-SUBMITTING PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEET(S) FOR COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE BE SURE ALL REVIEWS ARE DONE
 BEFORE MAKING ANY CORRECTIONS, DUE TO
 ANY POSSIBLE COMMENTS FROM OTHER
 REVIEW(ERS).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]