2004-11-30 00:00:00 | *********** UNSAT ******** |
| |
| 1)NOTE: PLEASE SEE # OF CONDUCTORS |
| INDICATED ON RISER FROM METER TO MAIN. |
| THIS IS A 3-PHASE SERVICE, YET ONLY |
| SHOWS 3-CONDUCTORS. |
| |
| 2)NOTE: PLEASE ALSO SEE #OF CONDUCTORS |
| SHOWN IN A SINGLE 2" CONDUIT. PLEASE |
| SEE |
| TABLES IN CHAPTER 9 NEC FOR CONDUIT |
| FILL. |
| |
| 3)NOTE: PLEASE SEE AN EQUIPMENT |
| GROUNDING CONDUCTOR IS NOW SHOWN FROM |
| METER TO MAIN. AN EQUIPMENT GRND IS NOT |
| INSTALLED FROM METER TO THE FIRST MEANS |
| OF DISCONNECT. 250.6,250.24. |
| |
| 4)NOTE: PLEASE CORRELATE RISER WITH |
| PANEL "A" FEEDER SCHEDULE, AS ON NOTES |
| ABOVE. |
| |
| 5)NOTE: PLEASE SEE RE-SUB SHEET |
| MENTIONS |
| PERMIT APPLIACTION TO BE BROUGHT IN BY |
| THE 11/24. THIS IS REQUIRED WHEN |
| RE-SUBMITTING PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| INSERT NEW SHEET(S) FOR COMPLETE SETS |
| FOR REVIEW AND STAMPING. |
| |
| PLEASE BE SURE ALL REVIEWS ARE DONE |
| BEFORE MAKING ANY CORRECTIONS, DUE TO |
| ANY POSSIBLE COMMENTS FROM OTHER |
| REVIEW(ERS). |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |