2004-12-14 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| IGNORE COMMENT #2 BELOW.ARCHITECT OF |
| RECORD REDLINED, SIGNED AND DATED A |
| HANDWRITTEN NOTE, GIVING WINDOW TYPE |
| AND SIZE. THE OTHER COMMENTS STILL |
| APPLY |
| |
| |
2004-12-10 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| THE MARION CONSTRUCTION COMMENT RESPONSE |
| LETTER DATED 11/22/04 IS NOTED WITH THE |
| FOLLOWING COMMENTS: |
| |
| 1) THE DOORS AND WINDOWS IN THE NEW |
| METAL BUILDING ARE STATED TO BE PART OF |
| THE METAL BUILDING DESIGN SUBMITTAL |
| PACKAGE BUT AS OF 12/10/04 THAT PACKAGE |
| HAS NOT BEEN SUBMITTEDTO THIS OFFICE. |
| THE DOOR AND WINDOW PRODUCT APPROVALS |
| ARE REQUIRED BEFORE THE PERMIT CAM BE |
| ISSUED. |
| |
| 2) SUBMITTAL OF A PRODUCT APPROVAL FOR |
| PGT SINGLE HUNG WINDOWS IS NOTED, BUT |
| THE PLANS DO NOT STATE THE SIZE OR TYPE |
| OF WINDOWS SO THAT THE DESIGN WIND |
| PRESSURES GIVEN IN THE PRODUCT APPROVAL |
| MAY BE VERIFIED. |
| |
| --PROVISO-- |
| A SEPARATE PERMIT APPLICATION AND |
| PRODUCT APPROVAL PACKAGE WILL BE |
| REQUIRED FOR THE BUILT-UP ROOFING. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |