Plan Review Notes
Plan Review Notes For Permit 03110607
Permit Number 03110607
Review Stop B
Sequence Number 3
Notes
Date Text
2004-12-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 IGNORE COMMENT #2 BELOW.ARCHITECT OF
 RECORD REDLINED, SIGNED AND DATED A
 HANDWRITTEN NOTE, GIVING WINDOW TYPE
 AND SIZE. THE OTHER COMMENTS STILL
 APPLY
  
  
2004-12-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 THE MARION CONSTRUCTION COMMENT RESPONSE
 LETTER DATED 11/22/04 IS NOTED WITH THE
 FOLLOWING COMMENTS:
  
 1) THE DOORS AND WINDOWS IN THE NEW
 METAL BUILDING ARE STATED TO BE PART OF
 THE METAL BUILDING DESIGN SUBMITTAL
 PACKAGE BUT AS OF 12/10/04 THAT PACKAGE
 HAS NOT BEEN SUBMITTEDTO THIS OFFICE.
 THE DOOR AND WINDOW PRODUCT APPROVALS
 ARE REQUIRED BEFORE THE PERMIT CAM BE
 ISSUED.
  
 2) SUBMITTAL OF A PRODUCT APPROVAL FOR
 PGT SINGLE HUNG WINDOWS IS NOTED, BUT
 THE PLANS DO NOT STATE THE SIZE OR TYPE
 OF WINDOWS SO THAT THE DESIGN WIND
 PRESSURES GIVEN IN THE PRODUCT APPROVAL
 MAY BE VERIFIED.
  
 --PROVISO--
 A SEPARATE PERMIT APPLICATION AND
 PRODUCT APPROVAL PACKAGE WILL BE
 REQUIRED FOR THE BUILT-UP ROOFING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]