Plan Review Notes
Plan Review Notes For Permit 03110607
Permit Number 03110607
Review Stop M
Sequence Number 2
Notes
Date Text
2004-10-05 00:00:00PROVISO:
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED WITH NOTIFICATION TO ALARM &
 STROBE IN NORMALLY OCCUPIED AREAS 2001
 FBC(M) 606.2.1 & 606.4.1.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M) 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.