2004-10-15 00:00:00 | ************* UNSAT ************** |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| THIS IS REQUIRED AT THIS TIME. |
| |
| 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| -ING OF EM/EXT LTS. |
| |
| 3)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MCB TO PANEL |
| "B".? 250.110,250.24,250.122 |
| |
| 4)NOTE: PLEASE SEE PANEL "B" IS SHOWN ON |
| A SP BRKR SPACE? #29 PLEASE SEE FEED TO |
| PANEL "B" IS SHOWN AS A 3P-200A BRKR TO |
| PANEL "B" WHICH IS INDICATED AS A SINGLE |
| PHASE PANEL ON PANEL SCHEDULE INFORMAT- |
| -ION?? WHICH ONE? |
| |
| 5)NOTE: PLEASE SEE SPACE #28 ON PANEL |
| SCHEDULE "A". THIS SHOWS AN ADDITIONAL |
| 2-P60A BRKR FOR SUB PANEL "B". |
| PLEASE CLARIFY?? |
| IF THERE IS INDEED AN ADDITIONAL 60A |
| SUB-PANEL, PLEASE ALSO INCLUDE THIS ON |
| RISER DIAGRAM. |
| |
| 6 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| PLEASE SEE PLAN S DO NOT INLCUDE ANY |
| LOAD CALCULATIONS? |
| PLEASE SEE 220.3 FOR SPECIFIC LIGHTING |
| LOADS FOR HIGH-BAY FIXTURES ETC. |
| |
| 7)NOTE: PLEASE SEE 600.5 FOR REQUIRED |
| SIGN CIRCUIT. EXISTING OR NEW?? |
| |
| PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |