Plan Review Notes For Permit 03110607 |
Permit Number |
03110607 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-12-15 00:00:00 | DENIED: | | 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | REQUIRED PER 2001 FBC(M) 606.2.1. | | | | 2.FAN SHUTDOWN SHALL HAVE NOTIFICATION | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | AREAS PER 2001 FBC(M) 606.4.1 & NFPA 90A | | 4-4.4.3. | | | | 3.PLEASE INDICATE WHAT TYPE OF WORK | | WILL BE DONE IN THE WAREHOUSE (WELDING, | | PREFAB OF PIPE?). | | | | 4.INDICATE IF ANY HAZARDOUS MATERIALS | | OR GASES WILL STORED ON SITE. | | | | 5.CONDENSER UNITS LOCATED ON THE ROOF | | SHALL COMPLY WITH 2001 FBC 1511.7. | | | | 6.PROVIDE OUTSIDE AIR CALCULATIONS PER | | 2001 FBC(M) 403.3. | | | | 7.PLEASE NOTE, EQUIPMENT LOCATED ON | | THE ROOFS WHERE ACCESS IS GREATER THAN | | 16 FT, A PERMANENT MEANS OF ACCESS SHALL | | BE PROVIDED. 2001 FBC(M) 306.5 | | | | 8.PLEASE PROVIDE INFORMATION ON THE | | CONDENSATE.PLAN SHEET M-1 NOTE 15 | | INDICATES CONDENSATE TO THE EXTERIOR. | | PLEASE PROVIDE PIPE LAYOUT. CONDENSATE | | SHALL TERMINATE A MINIMUM OF 12" FROM | | THE BUILDING STRUCTURE PER 2001 FBC | | 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|