2003-12-15 00:00:00DENIED:
 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 2001 FBC(M) 606.2.1.
  
 2.FAN SHUTDOWN SHALL HAVE NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS PER 2001 FBC(M) 606.4.1 & NFPA 90A
 4-4.4.3.
  
 3.PLEASE INDICATE WHAT TYPE OF WORK
 WILL BE DONE IN THE WAREHOUSE (WELDING,
 PREFAB OF PIPE?).
  
 4.INDICATE IF ANY HAZARDOUS MATERIALS
 OR GASES WILL STORED ON SITE.
  
 5.CONDENSER UNITS LOCATED ON THE ROOF
 SHALL COMPLY WITH 2001 FBC 1511.7.
  
 6.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 403.3.
  
 7.PLEASE NOTE, EQUIPMENT LOCATED ON
 THE ROOFS WHERE ACCESS IS GREATER THAN
 16 FT, A PERMANENT MEANS OF ACCESS SHALL
 BE PROVIDED. 2001 FBC(M) 306.5
  
 8.PLEASE PROVIDE INFORMATION ON THE
 CONDENSATE.PLAN SHEET M-1 NOTE 15
 INDICATES CONDENSATE TO THE EXTERIOR.
 PLEASE PROVIDE PIPE LAYOUT. CONDENSATE
 SHALL TERMINATE A MINIMUM OF 12" FROM
 THE BUILDING STRUCTURE PER 2001 FBC
 1503.4.4.
  