Plan Review Notes
Plan Review Notes For Permit 03110607
Permit Number 03110607
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-11-26 00:00:001) BUILDING ADDRESS REQUIRED. 6" HIGH
 NUMBERS ARE REQUIRED.
  
 2) 10" TREADS ARE NOT PERMITTED ON
 STAIRS. EXIT STAIRS FROM SECOND FLOOR
 THAT LEADS TO THE EXTERIOR DISPLAYS
 10" TREADS.
  
 3) HOW DOES FIRE AND PARAMEDICAL
 EQUIPMENT GAIN ACCESS THRU NEW GATE.
  
 4) DEMOLITION ACTIVITIES TO COMPLY
 WITH NFPA 241, THE STANDARD FOR
 DEMOLITION, RENOVATION, AND CONSTRUCTION
  
 5) SITE PLAN DOES NOT INDICATE ANY
 EXISTING OR NEW FIRE HYDRANTS FOR THE
 VICINITY.
  
 6) PLEASE PROVIDE HEIGHTS OF THE
 PROPOSED STORAGE RACKS.
  
 7) THE 42" AISLE NEAR THE DISPATCH
 AREA SHALL BE AT LEAST 44" WIDE.
  
 8) WHAT IS PLANNED TO BE STORED ON
 THE STORAGE RACKS.
  
 9) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 10) THE 2668 DOOR FOR THE STORAGE ROOM
 UNDER THE STAIRS SHALL BE AT LEAST
 45 MINUTE FIRE RATED.
  
 11) NO INDICATION THAT THE STORAGE
 ROOM OR STAIR DOOR ARE RATED AT THE
 SECOND FLOOR/MEZZANINE PLAN.
  
 12) TACTILE SIGNAGE REQUIRED AT STAIRS.
  
 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GAURDRAILS.
  
 14) ARE ANY EMERGENCY LIGHTS PRESENT
 IN THE STAIRS. ALSO ARE ALL EXIT
 SIGNS SHOWN ON E-1. NO EMERGENCY
 LIGHTING IN WAREHOUSE.
  
 15) WELDER NOTED ON PAGE E-3. ALL
 WELDING MUST BE APPROVED BY THE
 BUREAU OF FIRE PREVENTION. ALL
 WELDING OPERATIONS TO COMPLY WITH
 NFPA 51B. A CLEAR RADIUS OF 35 FEET
 IS REQUIRED FROM WELDING TO COMBUSTIBLES
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910