2003-11-26 00:00:00 | 1) BUILDING ADDRESS REQUIRED. 6" HIGH |
| NUMBERS ARE REQUIRED. |
| |
| 2) 10" TREADS ARE NOT PERMITTED ON |
| STAIRS. EXIT STAIRS FROM SECOND FLOOR |
| THAT LEADS TO THE EXTERIOR DISPLAYS |
| 10" TREADS. |
| |
| 3) HOW DOES FIRE AND PARAMEDICAL |
| EQUIPMENT GAIN ACCESS THRU NEW GATE. |
| |
| 4) DEMOLITION ACTIVITIES TO COMPLY |
| WITH NFPA 241, THE STANDARD FOR |
| DEMOLITION, RENOVATION, AND CONSTRUCTION |
| |
| 5) SITE PLAN DOES NOT INDICATE ANY |
| EXISTING OR NEW FIRE HYDRANTS FOR THE |
| VICINITY. |
| |
| 6) PLEASE PROVIDE HEIGHTS OF THE |
| PROPOSED STORAGE RACKS. |
| |
| 7) THE 42" AISLE NEAR THE DISPATCH |
| AREA SHALL BE AT LEAST 44" WIDE. |
| |
| 8) WHAT IS PLANNED TO BE STORED ON |
| THE STORAGE RACKS. |
| |
| 9) PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATIONS FOR WALLS AND |
| CEILINGS. |
| |
| 10) THE 2668 DOOR FOR THE STORAGE ROOM |
| UNDER THE STAIRS SHALL BE AT LEAST |
| 45 MINUTE FIRE RATED. |
| |
| 11) NO INDICATION THAT THE STORAGE |
| ROOM OR STAIR DOOR ARE RATED AT THE |
| SECOND FLOOR/MEZZANINE PLAN. |
| |
| 12) TACTILE SIGNAGE REQUIRED AT STAIRS. |
| |
| 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR ALL HANDRAILS AND |
| GAURDRAILS. |
| |
| 14) ARE ANY EMERGENCY LIGHTS PRESENT |
| IN THE STAIRS. ALSO ARE ALL EXIT |
| SIGNS SHOWN ON E-1. NO EMERGENCY |
| LIGHTING IN WAREHOUSE. |
| |
| 15) WELDER NOTED ON PAGE E-3. ALL |
| WELDING MUST BE APPROVED BY THE |
| BUREAU OF FIRE PREVENTION. ALL |
| WELDING OPERATIONS TO COMPLY WITH |
| NFPA 51B. A CLEAR RADIUS OF 35 FEET |
| IS REQUIRED FROM WELDING TO COMBUSTIBLES |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |