2003-12-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) FBC 13-103.1.1.1ENERGY CODE
 COMPLIANCE FORM.THE ELECTRICAL SYSTEM
 DESIGNER, LIGHTING SYSTEM DESIGNER,
 MECHANICAL SYTEM DESIGNER AND PLUMBING
 SYSTEM DESIGNER ENTRIES ON SHEET 2 OF
 FORM SHALL EACH BE COMPLETED BY THE
 SYSTEM DESIGNER, IN THIS CASE THE
 ARCHITECT, TO CERTIFY COMPLIANCE FOR
 THOSE SYSTEMS.
  
 4) FBC 303.1 ABD FBC 312.1WAREHOUSE:
 STORAGE OCCUPANCY V HAZARDOUS OCCUPANCY.
 ANNOTATE THE PLANS TO STATE WHAT TYPE
 AND QUANTITIES OF MATERIALS ARE TO BE
 STORED, SO THAT ANY HAZARDOUS (GROUP H)
 OCCUPANCY CAN BE DETERMINED.
  
 5) FBC* F102.2.4ROOF COVERINGS IN THE
 FIRE DISTRICT SHALL CONFORM TO THE
 REQUIREMENTS OF CLASS A OR B
 (REF: FBC 1505).ANNOTATE THE PLANS TO
 MEET THIS REQUIREMENT WITH RESPECT TO
 THE NEW ROOF, AND THE NEW ROOFING
 MATERIALS PROPOSED FOR THE EXISTING ROOF
  
 6) FBC* F102.2.5FIRE RESISTANCE FOR
 BUILDINGS IN THE FIRE DISTRICT.
 BUILDINGS GREATER THAN ONE STOREY, WHICH
 ARE NOT EITHER SPRINKLERED THROUGHOUT OR
 SURROUNDED ON ALL SIDES BY A PERMANENTLY
 OPEN SPACE OF LEAST 30 FT, SHALL HAVE
 ALL WALLS, FLOORS, ROOFS AND THEIR
 SUPPORTING STRUCTURAL MEMBERS AT LEAST
 1-HOUR FIRE RESISTANT.AMEND THE PLANS.
  
 7) FBC* F102.2.6FIRE RESISTANCE FOR
 EXTERIOR WALLS OF TYPE IV BUILDINGS IN
 THE FIRE DISTRICT.FOR TYPE IV
 BUILDINGS, EXTERIOR WALLS WITHIN 30 FT
 OF A COMMON PROPERTY LINE SHALL BE AT
 LEAST 2-HOUR FIRE-RESISTANT.AMEND THE
 PLANS.
  
 8) FBC TABLE 600NORTH EXTERIOR WALL.
 THE 2ND FLOOR PLAN ON SHEET A-2 SHOWS AN
 OPENING FOR AN EXHAUST FAN.A FIRE
 DAMPER OR ALTERNATIVE APPROVED MEANS OF
 PROTECTION SHALL BE PROVIDED IN
 ACCORDANCE WITH FBC 705.1.1.2.AMEND/
 ANNOTATE THE PLANS.
  
 9) FBC TABLE 600AND FBC* F102.2FOR
 THOSE EXTERIOR WALLS REQUIRED TO BE FIRE
 RESISTANT, THE COLUMNS, CLADDING RAILS,
 RAFTERS AND PURLINS, THAT PROVIDE
 SUPPORT AND LATERAL RESTRAINT TO THE
 WALL SHALL ALSO BE FIRE-RATED/PROTECTED.
  
 10) FBC* 104.2.1.2 SHEET S-1, FOUNDATION
 PLAN.AMEND THE PLAN TO SHOW THE SIZE
 AND DEPTH OF THE EXISTING FOOTINGS SHOWN
 ON SECTION A-3/2 TO RECEIVE ADDITIONAL
 LOAD FROM THE NEW MEZZANINE AND ROOF.
  
 11) FBC 2207 SHEET A-3, SECTIONS 2,3 & 4
 ANNOTATE THE PLANS TO REFERENCE AISC
 SPECIFICATIONS FOR FIELD WELDING,
 WORKMANSHIP, TECHNIQUE AND INSPECTION,
 AND THE QUALIFICATION OF THE WELDERS.
  
 12) FBC 1027.1.1 AND FBC 1027.2
 SHEET A-1, GROUND FLOOR PLAN OF THE
 STORAGE OCCUPANCY.THE ROLL-UP DOORS
 CANNOT BE CONSIDERED AS CONTRIBUTING TO
 THE EGRESS PROVISIONS SINCE EXIT DOORS
 MUST BE SWING DOORS CONFORMING TO THE
 REQUIREMENTS OF FBC 1012.1.2
 (REF: FBC 1027.2).A SINGLE EXIT IS NOT
 ACCEPTABLE AS THE MAXIMUM TRAVEL
 DISTANCE TO THE NEAREST EXIT WOULD
 EXCEED 50 FT (REF: FBC 1027.1.1).AMEND
 THE PLANS TO PROVIDE AT LEAST TWO EXIT
 DOORS FROM THE STORAGE AREA.
  
 13) FBC 1006.1.4THE SPACE UNDER THE
 NORTH STAIR SHALL BE ENCLOSED AND NON-
 USABLE, OR THE SOFFIT SHALL BE 1-HOUR
 FIRE-RESISTANT.
  
 14) FBC 1007.3SHEET A-1.THE NORTH
 STAIR IS SHOWN ON THIS SHEET WITH 10"
 TREADS.THE TREADS SHALL BE MIN 11".
 AMEND THE PLAN.
  
 15) FBC 1608.2HANDRAIL AND GUARDRAIL
 STRENGTH.AMEND THE PLANS TO STATE THE
 HANDRAIL AND GUARDRAIL STRENGTH
 REQUIREMENTS TO RESIST EACH OF THE
 CONCENTRATED LOADS AND LINEAR
 DISTRIBUTED LOADS REQUIRED BY THE CODE.
 THE 50 PLF STATED ON THE SHEET A-2,
 HANDRAIL DETAIL IS NOTED BUT DOES NOT
 COVER THE OTHER LOADING REQUIREMENTS
 REFERENCED ABOVE.
  
 16) FBC 11-4.26.3SHEET A-2.AMEND THE
 PLAN TO STATE THE REQUIREMENT FOR THE
 GRAB BARS AND THEIR MOUNTING AND
 FASTENERS TO RESIST A FORCE OF 250 LB
 APPLIED IN ANY DIRECTION WITHOUT
 EXCEEDING THE ALLOWABLE STRESS FOR THE
 MATERIAL.
  
 17) FBC 11-4.15SHEET A-2. WHAT APPEARS
 TO BE DETAILS OF DRINKING FOUNTAIN
 HEIGHTS AND CLEARANCES ARE INCORRECTLY
 TITLED "GRAB BARS AT WATER CLOSETS".
 AMEND THE TITLE.
  
 18) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, NEW AND REPLACEMENT WINDOWS,
 ROLL-UP DOOR, EXTERIOR DOOR AND STORM
 SHUTTERS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 19) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]