2003-12-03 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 3) MECHANICAL PLAN AND FLOOR PLAN DO NOT
 MATCH
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732