Date |
Text |
2004-01-30 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} REGARDING THE PANEL RELOCATION |
| SUBMITTHE FOLLOWING: |
| A) A RISER DIAGRAM OF RELOCATED |
| EQUIPMENT. |
| B) DISCONNECTING MEANS FOR THE CIRCUITS |
| REFEEDING THE HOUSE PER 225.31. |
| C) GROUNDING PER 250.32. |
| D) AIC FOR EQUIPMENT PER 110.9 & 110.10 |
| EVEN IF REUSING THE SAME EQUIPMENT |
| THE AIC CALC WILL CHANGE DEPENDING |
| ON THE LENGTH OF WIRE FROM THE |
| TRANSFORMER LOCATION. |
| |
| 2} A PANEL SCHEDULE INDICATING WIRE AND |
| OCP SIZES SO AS TO DETERMINE COMPLIANCE |
| WITH CODE ARTICLES IG: 210.11(C)(1),(2) |
| & (3). 210.12 ETC. |
| |
| 3} A LOAD CALCULATION PER 215.5. |
| |
| 4} INDICATE COMPLIANCE WITH 210.63 IF |
| APPLICABLE. |
| |
| 5} INDICATE COMPLIANCE WITH 210.52(E). |
| |
| 6} THERE MAY BE ADDITIONAL COMMENTS WHEN |
| THE PLANS ARE RESUBMITTED FROM THE |
| ARCHITECT. |
| |
| 7} PLEASE NOTE THAT TWO SETS OF PLANS |
| ARE REQUIRED TO BE SUBMITTED FOR REVIEW |
| PER 104 FBC. |
| |
| 8} ALL PLANS CONTAINING AN ARCHITECTS |
| SEAL ARE REQUIRED TO BE PREPARED BY HIM. |
| PLEASE ALSO INCLUDE CERTIFICATE OF |
| AUTHORIZATION NUMBERS WHERE REQUIRED. |
| ALSO A TITLE BLOCK IS REQUIRED.SEE |
| FS 481.219, FAC 61G1-16.004 FOR ABOVE |
| STATED REQUIREMENTS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |