Plan Review Notes
Plan Review Notes For Permit 03110552
Permit Number 03110552
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} REGARDING THE PANEL RELOCATION
 SUBMITTHE FOLLOWING:
 A) A RISER DIAGRAM OF RELOCATED
 EQUIPMENT.
 B) DISCONNECTING MEANS FOR THE CIRCUITS
 REFEEDING THE HOUSE PER 225.31.
 C) GROUNDING PER 250.32.
 D) AIC FOR EQUIPMENT PER 110.9 & 110.10
 EVEN IF REUSING THE SAME EQUIPMENT
 THE AIC CALC WILL CHANGE DEPENDING
 ON THE LENGTH OF WIRE FROM THE
 TRANSFORMER LOCATION.
  
 2} A PANEL SCHEDULE INDICATING WIRE AND
 OCP SIZES SO AS TO DETERMINE COMPLIANCE
 WITH CODE ARTICLES IG: 210.11(C)(1),(2)
 & (3). 210.12 ETC.
  
 3} A LOAD CALCULATION PER 215.5.
  
 4} INDICATE COMPLIANCE WITH 210.63 IF
 APPLICABLE.
  
 5} INDICATE COMPLIANCE WITH 210.52(E).
  
 6} THERE MAY BE ADDITIONAL COMMENTS WHEN
 THE PLANS ARE RESUBMITTED FROM THE
 ARCHITECT.
  
 7} PLEASE NOTE THAT TWO SETS OF PLANS
 ARE REQUIRED TO BE SUBMITTED FOR REVIEW
 PER 104 FBC.
  
 8} ALL PLANS CONTAINING AN ARCHITECTS
 SEAL ARE REQUIRED TO BE PREPARED BY HIM.
 PLEASE ALSO INCLUDE CERTIFICATE OF
 AUTHORIZATION NUMBERS WHERE REQUIRED.
 ALSO A TITLE BLOCK IS REQUIRED.SEE
 FS 481.219, FAC 61G1-16.004 FOR ABOVE
 STATED REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved