Plan Review Notes For Permit 03110332 |
Permit Number |
03110332 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-04-06 00:00:00 | DENIED: | | BUILDING WAS ORIGINALLY APPROVED FOR | | RESIDENTIAL.THE FOLLOWING SHALL BE | | ADDRESSED FOR CODE COMPLIANCE FOR | | COMMERCIAL STANDARDS: | | | | 1.OUTSIDE AIR CALCULATIONS PER 2001 | | FBC(M) 403.3. | | | | 2.INDICATE O.A. INTAKE, DUCT SIZE, | | MATERIAL, AND LAYOUT. | | | | 3.PLEASE CLARIFY RETURN TO THE AHU. | | IS THIS A PLENUM?PER 2001 FBC(M) | | 602.2.1, NO COMBUSTIBLES ALLOWED ABOVE | | THE CEILING IN THE RETURN AIR PLENUM. | | | | 4.DUCT SMOKE DETECTORS REQUIRED WHERE | | SYSTEMS HAVE AN AGGREGATE SUPPLY GREATER | | THAN 2,000 CFM.2001 FBC(M) 606.2.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|