2004-04-06 00:00:00DENIED:
 BUILDING WAS ORIGINALLY APPROVED FOR
 RESIDENTIAL.THE FOLLOWING SHALL BE
 ADDRESSED FOR CODE COMPLIANCE FOR
 COMMERCIAL STANDARDS:
  
 1.OUTSIDE AIR CALCULATIONS PER 2001
 FBC(M) 403.3.
  
 2.INDICATE O.A. INTAKE, DUCT SIZE,
 MATERIAL, AND LAYOUT.
  
 3.PLEASE CLARIFY RETURN TO THE AHU.
 IS THIS A PLENUM?PER 2001 FBC(M)
 602.2.1, NO COMBUSTIBLES ALLOWED ABOVE
 THE CEILING IN THE RETURN AIR PLENUM.
  
 4.DUCT SMOKE DETECTORS REQUIRED WHERE
 SYSTEMS HAVE AN AGGREGATE SUPPLY GREATER
 THAN 2,000 CFM.2001 FBC(M) 606.2.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.