2003-11-07 00:00:00******************** UNSAT *************
  
 RESIDENTIAL TO COMMERICAL
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE(
 S) TO BE SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
  
 2)NOTE: PLEASE SEE 600.5 FOR REQ'D
 SIGN CIRCUIT.
  
 3)NOTE: PLEASE SHOW LOAD CALC FOR
 COMMERICAL USE. PLEASE INCLUDE ALL
 CONTINUOUS LOADS AT 125%. 215.3,230.42
 ETC.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  