2003-12-08 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-PERCENTAGE OF OPENINGS SHOWN ON THE |
| SOUTH ELEVATION EXCEEDS THOSE ALLOWED |
| BY TABLE 600 FBC 2001. |
| **ALSO, SHOW ALL EXISTING OPENINGS ON |
| NORTH ELEVATION OF EXISTING BUILDING |
| TO CHECK TABLE 600 REQUIREMENTS. |
| 2-EXISTING FOOTING AT CARPORT AREA SEEMS |
| TO BE CONCRETE PAD FOR STEEL COLUMNS. |
| HOW IS THE CONCRETE EDGE REINFORCED |
| BETWEEN CONCRETE PADS?. NEED FOOTING |
| TO BE 12 BELOW GRADE (SEC. 1804.1.3 |
| FBC 2001 AND SEC. 1804.1.7 OF CITY |
| AMENDMENTS TO FBC 2001. |
| 3-PROVIDE SECTION/DETAIL AT CONNECTION |
| OF NEW WOOD FRAMING TO EXISTING STEEL |
| COLUMNS. SEC. 104.2.1.2 OF THE CITY |
| AMENDMENTS TO FBC 2001. |
| 4-CLARIFY INFORMATION GIVEN FOR MINIMUM |
| DESIGN PRESSURE. SEE COMMENTS ON PLANS |
| AND SEC. 1606.1.7 FBC 2001. EG: WHAT'S |
| A WIND PRESSURE B?. WHAT'S FS 18PSF?. |
| WHAT'S COMPONENT & CLADDING 36/MINUS |
| 48PSF?. |
| 5-WALL SECTION ON DRAWING #1: A)REVISE |
| TYPE OF NAILS FOR SIMPSON H9. SEE |
| SIMPSON CATALOGUE. |
| B)SPECIFY NAIL TYPE AND SPACING FOR FLAT |
| ROOF SHEATHING AND NEW WALL SHEATHING. |
| SEC. 2306 CITY AMENDMENTS TO FBC 2001. |
| C)CLARIFY WHERE ISSIMPSON PAHD42 |
| GOING TO BE INSTALLATED? SEC. 104.2.1 |
| CITY AMENDMENTS TO FBC 2001. |
| D)HOW ARE 2X4'S FASTENED TO BOTTOM PLATE |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| E)PROVIDE VENTILATION FOR FLAT ROOF AND |
| PITCHED ROOF AS REQUIRED BY SEC. |
| 2309.7 FBC 2001. |
| |
| 6-PROVIDE FLORIDA STATE PRODUCT APPROVAL |
| OR LOCAL PRODUCT APPROVAL FOR DOORS |
| WINDOWS, STORM SHUTTERS, FLAT ROOF, |
| METAL ROOF (IF REPLACED), FIXED WINDOW |
| (SEE SIZE ON PLANS), WALL SIDING |
| AS REQUIRED AFTER OCT. 1ST 2003. |
| PLEASE, SEE WWW.FLORIDABUILDING.ORG |
| FOR SPECIFIC INFORMATION REQUIRED. |
| 7-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS: |
| A)KEY PLAN AND INSTALLATION SCHEDULE. |
| B)CLEARLY MARK ON STORM SHUTTERS DWGS |
| SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| TYPE AND SPACING TO BE USED ACCORDING |
| TO DESIGN PRESSURES, EDGE DISTANCE, |
| CONNECTION TYPE, PANEL SPAN AND |
| STRUCTURE TO BE ATTACHED TO. |
| |
| 8-PROVIDE COMPLETE ENERGY CALCULATIONS |
| REPORT AND OWNER/AGENT TO SIGN & DATE |
| BOTTOM OF FORM AS WELL. |
| 9-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| BRING BACK STAMPED DRAWINGS AND PAID |
| RECEIPT. |
| 10-OWES $487.29 FOR LOW VALUATION AND |
| RADON FEES. |
| |
| |
| *IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ @ 805-6712. |
| |
| *PLEASE, RETURN REVIEWED SET AFTER |
| CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| TO EXPEDITE THE REVIEW PROCESS. |