2003-12-08 00:00:00BUILDING REVIEW CHECKLIST:
 1-PERCENTAGE OF OPENINGS SHOWN ON THE
 SOUTH ELEVATION EXCEEDS THOSE ALLOWED
 BY TABLE 600 FBC 2001.
 **ALSO, SHOW ALL EXISTING OPENINGS ON
 NORTH ELEVATION OF EXISTING BUILDING
 TO CHECK TABLE 600 REQUIREMENTS.
 2-EXISTING FOOTING AT CARPORT AREA SEEMS
 TO BE CONCRETE PAD FOR STEEL COLUMNS.
 HOW IS THE CONCRETE EDGE REINFORCED
 BETWEEN CONCRETE PADS?. NEED FOOTING
 TO BE 12 BELOW GRADE (SEC. 1804.1.3
 FBC 2001 AND SEC. 1804.1.7 OF CITY
 AMENDMENTS TO FBC 2001.
 3-PROVIDE SECTION/DETAIL AT CONNECTION
 OF NEW WOOD FRAMING TO EXISTING STEEL
 COLUMNS. SEC. 104.2.1.2 OF THE CITY
 AMENDMENTS TO FBC 2001.
 4-CLARIFY INFORMATION GIVEN FOR MINIMUM
 DESIGN PRESSURE. SEE COMMENTS ON PLANS
 AND SEC. 1606.1.7 FBC 2001. EG: WHAT'S
 A WIND PRESSURE B?. WHAT'S FS 18PSF?.
 WHAT'S COMPONENT & CLADDING 36/MINUS
 48PSF?.
 5-WALL SECTION ON DRAWING #1: A)REVISE
 TYPE OF NAILS FOR SIMPSON H9. SEE
 SIMPSON CATALOGUE.
 B)SPECIFY NAIL TYPE AND SPACING FOR FLAT
 ROOF SHEATHING AND NEW WALL SHEATHING.
 SEC. 2306 CITY AMENDMENTS TO FBC 2001.
 C)CLARIFY WHERE ISSIMPSON PAHD42
 GOING TO BE INSTALLATED? SEC. 104.2.1
 CITY AMENDMENTS TO FBC 2001.
 D)HOW ARE 2X4'S FASTENED TO BOTTOM PLATE
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 E)PROVIDE VENTILATION FOR FLAT ROOF AND
 PITCHED ROOF AS REQUIRED BY SEC.
 2309.7 FBC 2001.
  
 6-PROVIDE FLORIDA STATE PRODUCT APPROVAL
 OR LOCAL PRODUCT APPROVAL FOR DOORS
 WINDOWS, STORM SHUTTERS, FLAT ROOF,
 METAL ROOF (IF REPLACED), FIXED WINDOW
 (SEE SIZE ON PLANS), WALL SIDING
 AS REQUIRED AFTER OCT. 1ST 2003.
 PLEASE, SEE WWW.FLORIDABUILDING.ORG
 FOR SPECIFIC INFORMATION REQUIRED.
 7-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS:
 A)KEY PLAN AND INSTALLATION SCHEDULE.
 B)CLEARLY MARK ON STORM SHUTTERS DWGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO DESIGN PRESSURES, EDGE DISTANCE,
 CONNECTION TYPE, PANEL SPAN AND
 STRUCTURE TO BE ATTACHED TO.
  
 8-PROVIDE COMPLETE ENERGY CALCULATIONS
 REPORT AND OWNER/AGENT TO SIGN & DATE
 BOTTOM OF FORM AS WELL.
 9-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
 10-OWES $487.29 FOR LOW VALUATION AND
 RADON FEES.
  
  
 *IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ @ 805-6712.
  
 *PLEASE, RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DWGS
 TO EXPEDITE THE REVIEW PROCESS.