2003-12-17 00:00:00 | DENIED |
| |
| 1) THE IMPACT FEE INFORMATION IS NOT |
| FILLED IN ON THE STAMP ON SHEET C1. THE |
| REVIEW NUMBER AND THE SQUARE FOOTAGE ARE |
| REQUIRED TO BE ON THE STAMP. |
| |
| 2) SUBMIT COMPLETE SOIL TEST REPORT WITH |
| SOIL BEARING INFORMATION AND SOIL |
| PREPARATION RECOMMENDATIONS. SEE CITY OF |
| WPB AMENDMENTS TO FBC 1804.2.2. |
| |
| 3) REVISE THE HEAD/JAMB (SGD) DETAIL ON |
| A5 TO STATE THAT FRAME IS FASTENED |
| THROUGH THE 1X BUCK. |
| |
| 4) PROVIDE A ROOF SHEATHING FASTENER |
| SCHEDULE ON THE PLANS. PLANS REFER TO A |
| DIAPHRAM NAILING SCHEDULE BUT NONE IS |
| PROVIDED. |
| |
| 5) SPECIFY THE UPLIFT VALUES FOR THE |
| CONNECTORS IN DETAILS 9 AND 10 ON S4. |
| |
| 6) THE USP HLPTA 75 CONNECTORS SPECIFIED |
| IN THE TRUSS ANCHOR SCHEDULE SCHEDULE |
| ARE NOT LISTED IN THE 2003 USP CATALOG |
| AND ARE NOT LISTED ON THE STATE PRODUCT |
| APPROVAL WEBSITE. REVISE THE SCHEDULE |
| AND SPECIFY AN APPROVED CONNECTOR. |
| SEE 2003 USP CATALOG AND STATE WEBSITE. |
| |
| 7)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL ON THE |
| CITY OF WPB FORM PER RULE 9B-72. SEE |
| ATTACHMENT. |
| |
| 8) SUBMIT PRODUCT APPROVALS FOR THE |
| FOLLOWING: |
| - DOUBLE OUTSWING DOOR UNIT (ENTRY) |
| - SINGLE OUTSWING GLAZED DOOR(SIDE DOOR) |
| - MULLIONS (ONE SUBMITTED IS EXPIRED) |
| - 16' WIDE GARAGE DOOR (ALSO EXPIRED) |
| |
| 9) SUBMIT PRODUCT APPROVALS, KEY PLAN & |
| INSTALLATION SCHEDULE FOR STORM PANELS. |
| CLEARLY MARK ON THE DRAWINGS THE |
| SPECIFIC MOUNTING CONDITIONS AND ANCHOR |
| TYPE & SPACING. INFO MUST BE SUBMITTED |
| OR A SEPARATE PERMIT WILL BE REQUIRED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |