Plan Review Notes
Plan Review Notes For Permit 03110048
Permit Number 03110048
Review Stop E
Sequence Number 4
Notes
Date Text
2004-03-03 00:00:00************* UNSAT *************
  
 1)NOTE : PLANS NOW HAVE TITLE BLOCK
 REMOVED. HOWEVER, PLANS ARE STILL REQUI-
 -RED TO BE SIGNED BY THE PERSON EAL
 RESPONSIBLE FOR THE PLANS. 104.2.1 FBC
 IF ITS AN ARCH/ENGINEER, THEN SIGNED,
 DATED AND SEALED ALONG WITH THE TITLE
 BLOCK.
 FS 471/481, 61G15-23.002, 61G1-16.004
  
 2)NOTE: PLEASE SEE PLANS NOW HAVE
 PANEL SCHEDULE AS REQUESTED ON FIRST
 REVIEW, HOWEVER, PLEASE SEE THE FOLLOW-
 -ING COMMENTS. ALSO, SOME COMMENTS FROM
 FIRST REVIEW ARE NOT CLEAR.
  
 3)NOTE: PLEASE SEE PLANS, ONLY SHOWS A
 METER ON THE OUTSIDE OF HOUSE. RISER
 SEEMS TO INDICATE TWO MCB PANELS OUTSIDE
 ?? AND SHOWS TWO 2" CONDUITS FROM TOP TO
 INSIDE PANELS?? PLEASE CORRELATE PLANS.
 ONLY TWO PANEL SCHEDULES ARE SUBMITTED.
  
 4)NOTE: PLEASE ALSO SEE PANELS SCHEDULES
 SUBMITTED, THEY ARE NOW SHOWN AS 400A
 MCB PANELS, WHICH WOULD MAKE THE SERVICE
 800A'S?? RISER SHOWS AS 200A EACH??
 PLEASE CORRELATE AND INDICATE AMPERAGE
 OF METERCAN.
  
 5)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU'S/HEAT. PLEASE SEE PANEL "B",
 SHOWS 30A OCP FOR 10KW HEAT.?
 PLEASE CORRELATE PANEL SCHEDULES AND
 LOAD CALCULATIONS.
  
 6)NOTE: PLEASE SEE SM APPL LOADS SHOWN
 ON LOAD CALCULATIONS. ONLY SHOWS TWO,YET
 PANEL SCHEDULES INDICATE 4. PLEASE SEE
 220.16, 1500VA FOR EACH SM APPL.
  
 7)NOTE: PLANS INDICATE A GAS POOL HEATER
 AND LOAD CALCAULTIONS SHOWS ELECTRICAL
 POOL HEATER?? PLEASE ALSO SEE PANEL
 SCHEDULES DO NOT INDICATE POOL HEATER??
  
 8)NOTE: PLEASE CLARIFY TWO WHIRLPOOL
 TUBS. FLOOR PLANS ONLY SHOW ONE.
 PLEASE CORRELATE.
  
 9)NOTE: PANEL SCHEDULES INDICATE 45 CIR
 PANELS?? ALSO INDICATE ALL CIRCUITS ON
 RIGHT HAND SIDE AFTER (30) BEING THE
 SAME CIRCUIT #'S ON EACH SIDE???
  
 10)NOTE: PLEASE SEE WHIRLPOOL TUB ON
 PLANS, DO NOT INDICATE A GFI RECEPT.??
  
 PLEASE CORRELATE PLANS AND ADDRESS THE
 ABOVE COMMENTS. PLEASE SUBMIT FOR REVIEW
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  