2004-03-03 00:00:00 | ************* UNSAT ************* |
| |
| 1)NOTE : PLANS NOW HAVE TITLE BLOCK |
| REMOVED. HOWEVER, PLANS ARE STILL REQUI- |
| -RED TO BE SIGNED BY THE PERSON EAL |
| RESPONSIBLE FOR THE PLANS. 104.2.1 FBC |
| IF ITS AN ARCH/ENGINEER, THEN SIGNED, |
| DATED AND SEALED ALONG WITH THE TITLE |
| BLOCK. |
| FS 471/481, 61G15-23.002, 61G1-16.004 |
| |
| 2)NOTE: PLEASE SEE PLANS NOW HAVE |
| PANEL SCHEDULE AS REQUESTED ON FIRST |
| REVIEW, HOWEVER, PLEASE SEE THE FOLLOW- |
| -ING COMMENTS. ALSO, SOME COMMENTS FROM |
| FIRST REVIEW ARE NOT CLEAR. |
| |
| 3)NOTE: PLEASE SEE PLANS, ONLY SHOWS A |
| METER ON THE OUTSIDE OF HOUSE. RISER |
| SEEMS TO INDICATE TWO MCB PANELS OUTSIDE |
| ?? AND SHOWS TWO 2" CONDUITS FROM TOP TO |
| INSIDE PANELS?? PLEASE CORRELATE PLANS. |
| ONLY TWO PANEL SCHEDULES ARE SUBMITTED. |
| |
| 4)NOTE: PLEASE ALSO SEE PANELS SCHEDULES |
| SUBMITTED, THEY ARE NOW SHOWN AS 400A |
| MCB PANELS, WHICH WOULD MAKE THE SERVICE |
| 800A'S?? RISER SHOWS AS 200A EACH?? |
| PLEASE CORRELATE AND INDICATE AMPERAGE |
| OF METERCAN. |
| |
| 5)NOTE: PLEASE SEE 424.3B FOR MIN OCP |
| FOR AHU'S/HEAT. PLEASE SEE PANEL "B", |
| SHOWS 30A OCP FOR 10KW HEAT.? |
| PLEASE CORRELATE PANEL SCHEDULES AND |
| LOAD CALCULATIONS. |
| |
| 6)NOTE: PLEASE SEE SM APPL LOADS SHOWN |
| ON LOAD CALCULATIONS. ONLY SHOWS TWO,YET |
| PANEL SCHEDULES INDICATE 4. PLEASE SEE |
| 220.16, 1500VA FOR EACH SM APPL. |
| |
| 7)NOTE: PLANS INDICATE A GAS POOL HEATER |
| AND LOAD CALCAULTIONS SHOWS ELECTRICAL |
| POOL HEATER?? PLEASE ALSO SEE PANEL |
| SCHEDULES DO NOT INDICATE POOL HEATER?? |
| |
| 8)NOTE: PLEASE CLARIFY TWO WHIRLPOOL |
| TUBS. FLOOR PLANS ONLY SHOW ONE. |
| PLEASE CORRELATE. |
| |
| 9)NOTE: PANEL SCHEDULES INDICATE 45 CIR |
| PANELS?? ALSO INDICATE ALL CIRCUITS ON |
| RIGHT HAND SIDE AFTER (30) BEING THE |
| SAME CIRCUIT #'S ON EACH SIDE??? |
| |
| 10)NOTE: PLEASE SEE WHIRLPOOL TUB ON |
| PLANS, DO NOT INDICATE A GFI RECEPT.?? |
| |
| PLEASE CORRELATE PLANS AND ADDRESS THE |
| ABOVE COMMENTS. PLEASE SUBMIT FOR REVIEW |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |