Plan Review Notes
Plan Review Notes For Permit 03110048
Permit Number 03110048
Review Stop B
Sequence Number 3
Notes
Date Text
2004-03-11 00:00:00DENIED
  
 1) SUBMIT A SIGNED AND SEALED COPY OF A
 SUB-SURFACE SOIL TEST REPORT AS REQUIRED
 BY FBC 1804.2.2. THE REPORT SHALL
 CONTAIN THE CONCLUSIONS REACHED AS A
 RESULT OF THE TESTING AND SPECIFY THE
 SAFE BEARING CAPACITY OF THE SOIL.
  
 2)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE SAMPLE
 OF COVERSHEET FROM THE STATE WEBSITE FOR
 PGT SINGLE HUNG WINDOWS,ATTACHED.
 SUBMIT PRODUCT APPROVALS FOR EACH TYPE
 OF DOOR, WINDOW, ETC. THAT WILL BE
 INSTALLED IN THIS PROJECT.
  
 3) SUBMIT PRODUCT APPROVALS AS SPECIFIED
 ABOVE FOR THE FOLLOWING:
 - GARAGE DOORS
 - ARCHED WINDOWS
 - MULTIEDGED FIXED GLASS WINDOW
 - THREE PANEL SLIDING GLASS DOOR
 - CUSTOM DOORS AT ENTRY
 - SOLID CORE OUTSWING DOOR AT GARAGE
 - CASEMENT WINDOW
 - STRUCTURAL MULLIONS
  
 4) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 5) SPECIFY THE SIZES OF THE TWO ATTIC
 ACCESS OPENINGS AT THE SECOND FLOOR. SEE
 FBC 2309.6 (MIN.20"X 36").
  
 6) ENERGY CALCS. WERE NOT RESUBMITTED.
 SEE COMMENTS FROM SECOND REVIEW.
  
 7) SUBMIT MANUFACTURER'S SPECS. AND UL
 LISTING INFORMATION FOR THE GAS BBQ.
  
 8) SUBMIT SIGNED AND SEALED ENGINEERED
 SHOP DRAWINGS AND LAYOUT THAT HAS BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD.
  
 9) SPECIFY THE WELD TYPE FOR THE
 CONNECTION OF THE HAMBRO JOISTS TO THE
 STEEL EMBEDS.
  
 10)THE HAMBRO JOIST SPACING IS SPECIFIED
 AS 4'O.C. AND THE BEARING PLATES(EMBEDS)
 ARE SPACED 24"O.C. PLEASE CLARIFY. SEE
 SHEET S3.
  
 11) PROVIDE A DETAIL INDICATING THE
 ATTACHMENT OF THE CEILING TO THE HAMBRO
 FLOOR SYSTEM. INDICATE FURRING,FASTENERS
 SPACINGS,ETC.
  
 12) SPECIFY THE BRIDGING MATERIAL,
 SPACING, ATTCHMENT TO JOIST, ETC.FOR THE
 HAMBRO JOISTS ON THE PLANS.
  
 13) CORRECT THE TYPO IN THE STAIR NOTES
 ON D2 WHERE DBC SHOULD BE FBC.
  
 14) REVISE TRUSS CONNECTOR MARKS A4 AND
 A5 ON THE FIRST AND SECOND FLOOR ROOF
 PLANS ON S4 AND S5. THESE ID MARKS ARE
 NO LONGER LISTED IN THE REVISED TRUSS
 ANCHOR SCHEDULE.
  
 15) THE PRODUCT APPROVAL SUBMITTED FOR
 THE FRENCH DOORS IS FOR NON-IMPACT RATED
 DOORS. STORM PANELS WILL BE REQUIRED.
  
 16)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. UNLESS ALL
 EXTERIOR GLAZING IS IMPACT RATED.
  
 17) SEPARATE PERMITS WILL BE REQUIRED
 FOR OTHER TRADES THAT WERE NOT SIGNED ON
 PERMIT APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714