Plan Review Notes
Plan Review Notes For Permit 03110048
Permit Number 03110048
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLANS WERE SUBMITTED FOR PLAN
 REVIEW ON FIRST REVIEW AND CONTAINED A
 TITLE BLOCK FOR AN ENGINEER. PLANS HAVE
 SINCE COME BACK AND DO NOT CONATIN ANY
 INFORMATION FOR PLAN/DESIGN. AS REQ'D
 UNDER FBC 104.2.1
 PLANS ARE NOT REQ'D TO BE SIGNED AND
 SEALED UNLESS CONTAINING A TITLE BLOCK
 AND WERE DONE BY AN ARCH/ENG.
 PLANS STILL MUST BE NAMED AND SIGNED
 BY PERSON RESPONSIBLE FOR PLAN.
  
 2)NOTE: PLEASE SEE SERVICE, SHOWN AS
 400A SERVICE. SHOWS 42CIR MCB PANELS
 FEEDING SOME OTHER PANELS. PLANS ONLY
 SHOW TWO PANELS IN GARAGE AND NO MCB
 PANELS OUTSIDE WITH METER, AS RISER SHOW
 -S. PLEASE SEE FIRST SET OF NOTES
 ASKING FOR PANEL SCHEDULES.
  
 3)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 MIN REQ'D FOR BATH RECEPTS. SEE RECEPTS
 MISSING FROM BATH(S). PLEASE LIST AS REQ
 'D.
  
 4)NOTE: PLEASE SEE MISSING LT FOR BATH
 DOWNSTAIRS NEXT TO MEDIA/BEDRM.
 210.70
  
 5)NOTE: PLEASE SEE PLANS, PLEASE CLARIFY
 LOCATION OF AHU`S AND DISC'S. 440.11
  
 6)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66
 310.15B6 REQ'S MIN 400MC TOTAL FOR
 SEC'S, 250.66 SIZES GEC FOR 400MCM/
 WOULD BE 1/0.
  
 7)NOTE: PLEASE SEE GFI NOTE ABOVE RISER,
 SHOWS GFI W/IN 15' OF POOL. PLEASE SEE
 680.22A5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]