2004-01-21 00:00:00 | **************** UNSAT **************** |
| |
| 1)NOTE: PLANS WERE SUBMITTED FOR PLAN |
| REVIEW ON FIRST REVIEW AND CONTAINED A |
| TITLE BLOCK FOR AN ENGINEER. PLANS HAVE |
| SINCE COME BACK AND DO NOT CONATIN ANY |
| INFORMATION FOR PLAN/DESIGN. AS REQ'D |
| UNDER FBC 104.2.1 |
| PLANS ARE NOT REQ'D TO BE SIGNED AND |
| SEALED UNLESS CONTAINING A TITLE BLOCK |
| AND WERE DONE BY AN ARCH/ENG. |
| PLANS STILL MUST BE NAMED AND SIGNED |
| BY PERSON RESPONSIBLE FOR PLAN. |
| |
| 2)NOTE: PLEASE SEE SERVICE, SHOWN AS |
| 400A SERVICE. SHOWS 42CIR MCB PANELS |
| FEEDING SOME OTHER PANELS. PLANS ONLY |
| SHOW TWO PANELS IN GARAGE AND NO MCB |
| PANELS OUTSIDE WITH METER, AS RISER SHOW |
| -S. PLEASE SEE FIRST SET OF NOTES |
| ASKING FOR PANEL SCHEDULES. |
| |
| 3)NOTE: PLEASE SEE 210.52D,210.11C3 FOR |
| MIN REQ'D FOR BATH RECEPTS. SEE RECEPTS |
| MISSING FROM BATH(S). PLEASE LIST AS REQ |
| 'D. |
| |
| 4)NOTE: PLEASE SEE MISSING LT FOR BATH |
| DOWNSTAIRS NEXT TO MEDIA/BEDRM. |
| 210.70 |
| |
| 5)NOTE: PLEASE SEE PLANS, PLEASE CLARIFY |
| LOCATION OF AHU`S AND DISC'S. 440.11 |
| |
| 6)NOTE: PLEASE SIZE GROUNDING ELECTRODE |
| CONDUCTOR PER 250.66 |
| 310.15B6 REQ'S MIN 400MC TOTAL FOR |
| SEC'S, 250.66 SIZES GEC FOR 400MCM/ |
| WOULD BE 1/0. |
| |
| 7)NOTE: PLEASE SEE GFI NOTE ABOVE RISER, |
| SHOWS GFI W/IN 15' OF POOL. PLEASE SEE |
| 680.22A5 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |