Plan Review Notes
Plan Review Notes For Permit 03110048
Permit Number 03110048
Review Stop B
Sequence Number 2
Notes
Date Text
2004-01-26 00:00:00DENIED
  
 1) BOTH SETS OF PLANS ARE REQUIRED TO BE
 STAMPED BY PB COUNTY FOR IMPACT FEES.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF A
 SUB-SURFACE SOIL TEST REPORT AS REQUIRED
 BY FBC 1804.2.2.
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT FOR ALL WINDOWS, DOORS, GARAGE
 DOORS, STORM PANELS, TRUSS CONNECTORS,
 ETC. THAT IS SPECIFIED ON THE PLANS.
  
 4) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED BEFORE THE C.O. IS ISSUED.
  
 5) SPECIFY THE SIZES OF THE TWO ATTIC
 ACCESS OPENINGS ON THE SECOND FLOOR.
  
 6) THE CONDITIONED FLOOR AREA LISTED ON
 THE ENERGY CALC. FORM DOES NOT AGREE
 WITH THE A/C AREA LISTED ON THE PLANS.
 THE FORM IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER/AGENT.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BBQ ON
 THE LANAI.
  
 8) INDICATE THE BEAM ELEVATIONS (TOB)
 ON SHEETS S1 AND S2.
  
 9) SPECIFY ON THE PLANS THAT THE WIRE
 MESH WILL BE SUPPORTED ON APPROVED
 SUPPORTS AT NO MORE THAN 3'OC PER FBC
 1909.3.
  
 10) SUBMIT SIGNED AND SEALED ENGINEERING
 FOR THE HAMBRO FLOOR SYSTEM.
  
 11) PLEASE UPDATE THE ANCHOR SCHEDULES
 ON S4 AND S5. FAC RULE 9B-72 REQUIRES
 TRUSS CONNECTORS TO HAVE STATE PRODUCT
 APPROVAL. THERE IS NO USP RTPGA
 CONNECTOR LISTED. SEMCO AND HUGHES ARE
 NO LONGER IN BUSINESS AND ARE NOT LISTED
 WITH THE STATE, PLEASE REMOVE REFRENCES
 TO THEM.
  
 12) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS.INCREASE IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 REVISE TRUSS ANCHOR SCHEDULE WITH VALUES
 THAT DO NOT INCLUDE THIS STRESS INCREASE
 SEE LATEST USP CATALOG.
  
 13) SPECIFY FIREBLOCKING ON THE WALL
 SECTIONS ON D1 AT THE INTERSECTIONS OF
 THE CONCEALED VERTICAL AND HORIZONTAL
 SPACES. SEE FBC 2305.1.
  
 14) CLARIFY ON THE STAIR DETAILS ON D2
 THAT THE HANDRAILS FOR THE CIRCULAR
 STAIRS ARE BETWEEN 34" AND 38" ABOVE THE
 LEADING EDGE OF THE TREADS AS REQUIRED
 BY FBC 1007.5.
  
 15)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
 A SEPARATE PERMIT AND FEES WILL BE
 REQUIRED IF ALL INFORMATION IS NOT
 SUBMITTED BEFORE PERMIT IS ISSUED.
  
 16) SEPARATE PERMITS WILL BE REQUIRED
 FOR OTHER TRADES AS THEY WERE NOT SIGNED
 ONTO PERMIT APPLICATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714