Plan Review Notes For Permit 03110048 |
Permit Number |
03110048 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-12-03 00:00:00 | DENIED; | | 1.PLANS ARE NOT SIGNED OR SEALED. | | 2.PLUMBING RISER DIAGRAM DOES NOT MATCH | | FLOOR PLAN. | | A.MASTER BATH AND LAUNDRY ROOM ARE | | ON THE 1ST FLOOR ON FLOOR PLAN A-3 | | RISER DIAGRAM SHOWS 2ND FLOOR. | | B.LAUNDRY TUB CANNOT BE ON SAME | | STACK AS W/M BECAUSE FIXTURES ARE | | ON DIFFERENT SIDES OF ROOM. | | C.BUTLER PANTRY SINK NOT ON RISER | | DIAGRAM. | | D.HIS BATHROOM HAS SHOWER NOT TUB. | | E.RISER DIAGRAM SHOULD BE AN IMAGE | | OF THE FLOOR PLAN, FIXTURES ARE | | NOT IN PROPER ORDER. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|