2003-11-07 00:00:00 | *************** UNSAT **************** |
| |
| PLEASE SEE THAT PLANS ARE ONLY IN FOR |
| PLAN REVIEW AND NOT SUBMITTED FOR |
| PERMIT AT THIS TIME. |
| |
| 1)NOTE: PLANS WILL BE REQ'D TO BE SIGNED |
| DATED AND SEALED BY THE ARCH/ENGINEER |
| OF RECORD PER FS 471.025,481.221 |
| PLEASE NOTE: FBPE'S HAS GIVEN TO THIS |
| OFFICE INFORMATION THAT REQUIRES A |
| SIGNATURE THAT CONTAINS A MIN IF FIRST |
| AND LAST NAME. |
| |
| 2)NOTE: PLEASE SEE PLANS, SHOWS BOTH |
| PANEL IN GARAGE? PLEASE CLARIFY WHERE |
| METER LOCATION IS. PLEASE SEE LOCAL |
| AMENDMENTS, 210.70 NO MORE THAT 8' OF |
| UNPROTECTED CONDUCTOS INSIDE HOUSE. |
| |
| 3)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) |
| WITH CIRCUITS, AWG AND OCP REQ'D. 215.5 |
| PLEASE LIST THE REQUIRED ARC FAULT |
| PROTECTTION PER NEC 2002 210.12 |
| PLEASE LIST BATH(S) AS PER 210.52D AND |
| 210.11C3 AS 20A AND #12. ETC ETC |
| |
| 4)NOTE: PLEASE SEE PLANS SHOW 4 A/C COND |
| UNITS AND PLEASE SHOW AHU'S AND DISC PER |
| 440.11 |
| |
| 5)NOTE: PLEASE SEE 210.52E FOR MIN OF |
| FRONT AND REAR GFI RECEPTS. |
| |
| 6)NOTE: PLEASE SEE 210.52 FOR RECEPTS |
| REQUIRED FOR WALL SPACE, INCLUDING |
| RAIL AREAS. THERE IS MANY RECEPTS MISS- |
| ING UPSTAIRS. |
| |
| 7)NOTE: PLEASE SEE NFPA-72 8-1.4.2, |
| SD'S ARE NOT PERMITTED IN KITCHENS AND |
| INFACT MUST BE A MIN OF 3' FROM KITCHENS |
| AND BATHS. |
| PLEASE ALSO SEE THAT A SD IS REQ'D AT |
| THE BASE OF STAIRS LEADING TO THE FLOOR |
| ABOVE IN THE IMMEDIATE VICINITY OF STAIR |
| -S. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |