Plan Review Notes
Plan Review Notes For Permit 03110048
Permit Number 03110048
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-07 00:00:00*************** UNSAT ****************
  
 PLEASE SEE THAT PLANS ARE ONLY IN FOR
 PLAN REVIEW AND NOT SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 1)NOTE: PLANS WILL BE REQ'D TO BE SIGNED
 DATED AND SEALED BY THE ARCH/ENGINEER
 OF RECORD PER FS 471.025,481.221
 PLEASE NOTE: FBPE'S HAS GIVEN TO THIS
 OFFICE INFORMATION THAT REQUIRES A
 SIGNATURE THAT CONTAINS A MIN IF FIRST
 AND LAST NAME.
  
 2)NOTE: PLEASE SEE PLANS, SHOWS BOTH
 PANEL IN GARAGE? PLEASE CLARIFY WHERE
 METER LOCATION IS. PLEASE SEE LOCAL
 AMENDMENTS, 210.70 NO MORE THAT 8' OF
 UNPROTECTED CONDUCTOS INSIDE HOUSE.
  
 3)NOTE: PLEASE SUBMIT PANEL SCHEDULE(S)
 WITH CIRCUITS, AWG AND OCP REQ'D. 215.5
 PLEASE LIST THE REQUIRED ARC FAULT
 PROTECTTION PER NEC 2002 210.12
 PLEASE LIST BATH(S) AS PER 210.52D AND
 210.11C3 AS 20A AND #12. ETC ETC
  
 4)NOTE: PLEASE SEE PLANS SHOW 4 A/C COND
 UNITS AND PLEASE SHOW AHU'S AND DISC PER
 440.11
  
 5)NOTE: PLEASE SEE 210.52E FOR MIN OF
 FRONT AND REAR GFI RECEPTS.
  
 6)NOTE: PLEASE SEE 210.52 FOR RECEPTS
 REQUIRED FOR WALL SPACE, INCLUDING
 RAIL AREAS. THERE IS MANY RECEPTS MISS-
 ING UPSTAIRS.
  
 7)NOTE: PLEASE SEE NFPA-72 8-1.4.2,
 SD'S ARE NOT PERMITTED IN KITCHENS AND
 INFACT MUST BE A MIN OF 3' FROM KITCHENS
 AND BATHS.
 PLEASE ALSO SEE THAT A SD IS REQ'D AT
 THE BASE OF STAIRS LEADING TO THE FLOOR
 ABOVE IN THE IMMEDIATE VICINITY OF STAIR
 -S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]