2003-12-11 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) PLANS ARE REQUIRED TO BE SIGNED, |
| SEALED AND DATED BY THE DESIGNER OF |
| RECORD. |
| |
| 4) INDICATE IN THE DESIGN INFORMATION ON |
| A-3 THAT STRUCTURE IS DESIGNED AS |
| ENCLOSED. |
| |
| 5) SPECIFY THE REQUIRED BEARING CAPACITY |
| OF THE SOIL ON THE PLANS. |
| |
| 6) SUBMIT A SUB-SURFACE SOIL BEARING |
| TEST REPORT AS REQUIRED BY FBC 1804.2.2. |
| |
| 7) SPECIFY THE FINISH FLOOR ELEVATION ON |
| THE PLANS. THE STRUCTURE IS LOCATED IN |
| AN A5 FLOOD ZONE. A MINIMUM ELEVATION OF |
| 7'- 6" IS REQUIRED. AN ELEVATION |
| CERTIFICATE WILL BE REQUIRED FOR C.O. |
| |
| 8)PRODUCT APPROVALS SUBMITTED FOR PERMIT |
| APPLICATIONS AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. SUBMIT PRODUCT APPROVALS FOR |
| WINDOWS, DOORS, ROOFING, ETC. |
| |
| 9) SUBMIT A SURVEY AND SITE PLAN FOR |
| DETERMINING SETBACK REQUIREMENTS AND |
| FBC TABLE 600. |
| |
| 10) THE WORD WIDTH IS MISSING FROM THE |
| NET CLEAR OPENING FOR THE EGRESS WINDOWS |
| ON A-3. |
| |
| 11) SPECIFY THE SIZES OF THE ATTIC |
| ACCESSES ON A3 AND A4. |
| |
| 12) SPECIFY THE WINDOW TYPES ON THE |
| PLANS (I.E. SINGLE HUNG, FIXED, CASEMENT |
| ETC.). |
| |
| 13) THERE ARE ALOT OF ERRORS IN THE |
| WINDOW LEGEND AND ON THE PLANS. THE |
| SIZES & WINDOW TYPES, DO NOT CORRESPOND |
| TO ELEVATIONS. PLEASE CORRECT. |
| |
| 14) DIMENSION FROM FRONT OF STRUCTURE TO |
| FRONT OF COVERED ENTRY IS NOT GIVEN. |
| PROVIDE EXTERIOR WALL DIMENSIONS ON THE |
| FLOOR PLAN. |
| |
| 15) PROVIDE OVERALL DIMENSIONS FOR THE |
| WALL SECTIONS ON S1 AND S2. |
| |
| 16) SUBMIT UL LISTING INFORMATION FOR |
| THE BBQ GRILL ON LANAI. |
| |
| 17) PROVIDE AN EGRESS WINDOW AT THE |
| STUDY OR SPECIFY ON THE PLAN THAT THIS |
| ROOM WILL NOT BE USED FOR SLEEPING |
| PURPOSES. |
| |
| 18) INDICATE ON THE PLANS THAT TEMPERED |
| GLASS IS REQUIRED IN BATHROOM WINDOWS IF |
| SILL HEIGHT IS LESS THAN 60" ABOVE |
| STANDING AREA PER FBC 2405.2.1. (IMPACT |
| RESISTANT GLASS IS ACCEPTABLE) |
| |
| 19) THE SECOND FLOOR BEDROOMS ARE |
| REQUIRED TO COMPLY WITH FBC 1005.4 FOR |
| EGRESS WINDOWS. (5.7 SQFT CLEAR OPENING |
| AREA IS REQUIRED) |
| |
| 20) INDICATE THE TOP OF BEAM ELEVATIONS |
| ON SHEETS S1 AND S2. |
| |
| 21) CORRECT FOOTING SIZE FOR FOOTING AT |
| LIVING ROOM ON S1 THAT IS GIVEN AS 22"X |
| 42". |
| |
| 22) SPECIFY THE SLAB THICKNESS, WIRE |
| REINFORCEMENT SUPPORTED PER FBC 1909.3, |
| VAPOR BARRIER AND TERMITE TREATED SOIL. |
| |
| 23) INDICATE THAT TIE BEAM IS FOR THE |
| SECOND FLOOR IS 8"X 12" EXCEPT AT |
| OPENINGS. |
| |
| 24) SUBMIT SIGNED AND SEALED ENGINEERING |
| FOR THE HAMBRO FLOOR SYSTEM. |
| |
| 25) SUBMIT MORE COMPLETE DETAILS FOR THE |
| WOOD FRAME TOWER. SPECIFY DIMENSIONS, |
| FRAMING DETAILS, CONNECTORS, EXTERIOR |
| FINISH, FIRE BLOCKING, ETC. |
| |
| 26) PLEASE REVISE THE TRUSS ANCHOR |
| SCHEDULE S4 AND S5. THERE IS NO USP |
| RTPGA836 CONNECTOR LISTED IN THE 2003 |
| USP CATALOG OR ON THE STATE PRODUCT |
| APPROVAL LISTING. USE VALUES THAT DO NOT |
| INCLUDE A ONE THIRD INCREASE IN THE |
| STEEL CALCULATIONS PER FBC 1609.4.3. |
| REVIEW THE UPLIFT CAPACITY FOR THE A6 |
| CONNECTOR IN THE SCHEDULE. DUE TO THE |
| PROXIMITY OF THE THREE STRAPS, THE |
| UPLIFT CAPACITIES ARE REDUCED BECAUSE |
| OF OVERLAPPING CONE PULLOUTS OF THE |
| CONCRETE BEAMS. REMOVE THE REFERENCE TO |
| SEMCO AND HUGHES FROM THE SCHEDULES AS |
| THEY NO LONGER EXIST. |
| |
| 27) PROVIDE AN ID TAG ON S4 FOR THE |
| LEDGER THAT TIES IT TO THE DETAIL ON D2. |
| THE UPLIFT FOR ONE OF THE GIRDERS IS |
| 2100# WHICH EXCEEDS THE UPLIFT CAPACITY |
| OF THE HUS28 HANGER. PLEASE CORRECT. |
| |
| 28) PUT THE NOTE THAT CLARIFIES THE |
| DETAIL "O" AND "Q" ON SHEET S5 WHERE |
| THESE CONNECTORS ARE SPECIFIED. |
| |
| 29) REVISE THE ROOFING NAIL TYPE THAT IS |
| SPECIFIED ON D1. FOR A MEAN ROOF HEIGHT |
| GREATER THAN 25' USE 8D RING-SHANK NAILS |
| IN ZONE 3 AS REQUIRED BY THE CITY OF WPB |
| AMENDMENTS TO FBC TABLE 2306.1. |
| |
| 30) PROVIDE INTERIOR WALL DETAILS. |
| |
| 31) SPECIFY FIRE BLOCKING ON THE WALL |
| SECTIONS ON D1 AND THE TOWER DETAIL ON |
| D2. |
| |
| 32) THE 2 STORY WALL SECTION ON D1 SHOWS |
| PRECAST LINTELS AT OPENINGS AND THE |
| REST OF THE PLANS INDICATE POURED BEAMS. |
| PLEASE REVISE. |
| |
| 33) CLARIFY THE (2) 16" DIMENSIONS THAT |
| ARE SHOWN AT THE FOOTER ON THE 2 STORY |
| DETAIL ON D1. |
| |
| 34) PROVIDE ADDITIONAL DETAILS FOR THE |
| CIRCULAR STAIRS. SPECIFY THE WIDTH OF |
| THE STAIRS, HANDRAILS 34"- 38" ABOVE THE |
| LEADING EDGE OF TREADS PER FBC 1007.5, |
| GUARDRAILS WITH INTERMEDIATE RAILS PER |
| FBC 1015 AND SHOW COMPLIANCE WITH FBC |
| 1007.8.3 FOR MINIMUM TREAD DEPTHS. |
| |