Plan Review Notes
Plan Review Notes For Permit 03110048
Permit Number 03110048
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-11 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PLANS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD.
  
 4) INDICATE IN THE DESIGN INFORMATION ON
 A-3 THAT STRUCTURE IS DESIGNED AS
 ENCLOSED.
  
 5) SPECIFY THE REQUIRED BEARING CAPACITY
 OF THE SOIL ON THE PLANS.
  
 6) SUBMIT A SUB-SURFACE SOIL BEARING
 TEST REPORT AS REQUIRED BY FBC 1804.2.2.
  
 7) SPECIFY THE FINISH FLOOR ELEVATION ON
 THE PLANS. THE STRUCTURE IS LOCATED IN
 AN A5 FLOOD ZONE. A MINIMUM ELEVATION OF
 7'- 6" IS REQUIRED. AN ELEVATION
 CERTIFICATE WILL BE REQUIRED FOR C.O.
  
 8)PRODUCT APPROVALS SUBMITTED FOR PERMIT
 APPLICATIONS AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. SUBMIT PRODUCT APPROVALS FOR
 WINDOWS, DOORS, ROOFING, ETC.
  
 9) SUBMIT A SURVEY AND SITE PLAN FOR
 DETERMINING SETBACK REQUIREMENTS AND
 FBC TABLE 600.
  
 10) THE WORD WIDTH IS MISSING FROM THE
 NET CLEAR OPENING FOR THE EGRESS WINDOWS
 ON A-3.
  
 11) SPECIFY THE SIZES OF THE ATTIC
 ACCESSES ON A3 AND A4.
  
 12) SPECIFY THE WINDOW TYPES ON THE
 PLANS (I.E. SINGLE HUNG, FIXED, CASEMENT
 ETC.).
  
 13) THERE ARE ALOT OF ERRORS IN THE
 WINDOW LEGEND AND ON THE PLANS. THE
 SIZES & WINDOW TYPES, DO NOT CORRESPOND
 TO ELEVATIONS. PLEASE CORRECT.
  
 14) DIMENSION FROM FRONT OF STRUCTURE TO
 FRONT OF COVERED ENTRY IS NOT GIVEN.
 PROVIDE EXTERIOR WALL DIMENSIONS ON THE
 FLOOR PLAN.
  
 15) PROVIDE OVERALL DIMENSIONS FOR THE
 WALL SECTIONS ON S1 AND S2.
  
 16) SUBMIT UL LISTING INFORMATION FOR
 THE BBQ GRILL ON LANAI.
  
 17) PROVIDE AN EGRESS WINDOW AT THE
 STUDY OR SPECIFY ON THE PLAN THAT THIS
 ROOM WILL NOT BE USED FOR SLEEPING
 PURPOSES.
  
 18) INDICATE ON THE PLANS THAT TEMPERED
 GLASS IS REQUIRED IN BATHROOM WINDOWS IF
 SILL HEIGHT IS LESS THAN 60" ABOVE
 STANDING AREA PER FBC 2405.2.1. (IMPACT
 RESISTANT GLASS IS ACCEPTABLE)
  
 19) THE SECOND FLOOR BEDROOMS ARE
 REQUIRED TO COMPLY WITH FBC 1005.4 FOR
 EGRESS WINDOWS. (5.7 SQFT CLEAR OPENING
 AREA IS REQUIRED)
  
 20) INDICATE THE TOP OF BEAM ELEVATIONS
 ON SHEETS S1 AND S2.
  
 21) CORRECT FOOTING SIZE FOR FOOTING AT
 LIVING ROOM ON S1 THAT IS GIVEN AS 22"X
 42".
  
 22) SPECIFY THE SLAB THICKNESS, WIRE
 REINFORCEMENT SUPPORTED PER FBC 1909.3,
 VAPOR BARRIER AND TERMITE TREATED SOIL.
  
 23) INDICATE THAT TIE BEAM IS FOR THE
 SECOND FLOOR IS 8"X 12" EXCEPT AT
 OPENINGS.
  
 24) SUBMIT SIGNED AND SEALED ENGINEERING
 FOR THE HAMBRO FLOOR SYSTEM.
  
 25) SUBMIT MORE COMPLETE DETAILS FOR THE
 WOOD FRAME TOWER. SPECIFY DIMENSIONS,
 FRAMING DETAILS, CONNECTORS, EXTERIOR
 FINISH, FIRE BLOCKING, ETC.
  
 26) PLEASE REVISE THE TRUSS ANCHOR
 SCHEDULE S4 AND S5. THERE IS NO USP
 RTPGA836 CONNECTOR LISTED IN THE 2003
 USP CATALOG OR ON THE STATE PRODUCT
 APPROVAL LISTING. USE VALUES THAT DO NOT
 INCLUDE A ONE THIRD INCREASE IN THE
 STEEL CALCULATIONS PER FBC 1609.4.3.
 REVIEW THE UPLIFT CAPACITY FOR THE A6
 CONNECTOR IN THE SCHEDULE. DUE TO THE
 PROXIMITY OF THE THREE STRAPS, THE
 UPLIFT CAPACITIES ARE REDUCED BECAUSE
 OF OVERLAPPING CONE PULLOUTS OF THE
 CONCRETE BEAMS. REMOVE THE REFERENCE TO
 SEMCO AND HUGHES FROM THE SCHEDULES AS
 THEY NO LONGER EXIST.
  
 27) PROVIDE AN ID TAG ON S4 FOR THE
 LEDGER THAT TIES IT TO THE DETAIL ON D2.
 THE UPLIFT FOR ONE OF THE GIRDERS IS
 2100# WHICH EXCEEDS THE UPLIFT CAPACITY
 OF THE HUS28 HANGER. PLEASE CORRECT.
  
 28) PUT THE NOTE THAT CLARIFIES THE
 DETAIL "O" AND "Q" ON SHEET S5 WHERE
 THESE CONNECTORS ARE SPECIFIED.
  
 29) REVISE THE ROOFING NAIL TYPE THAT IS
 SPECIFIED ON D1. FOR A MEAN ROOF HEIGHT
 GREATER THAN 25' USE 8D RING-SHANK NAILS
 IN ZONE 3 AS REQUIRED BY THE CITY OF WPB
 AMENDMENTS TO FBC TABLE 2306.1.
  
 30) PROVIDE INTERIOR WALL DETAILS.
  
 31) SPECIFY FIRE BLOCKING ON THE WALL
 SECTIONS ON D1 AND THE TOWER DETAIL ON
 D2.
  
 32) THE 2 STORY WALL SECTION ON D1 SHOWS
 PRECAST LINTELS AT OPENINGS AND THE
 REST OF THE PLANS INDICATE POURED BEAMS.
 PLEASE REVISE.
  
 33) CLARIFY THE (2) 16" DIMENSIONS THAT
 ARE SHOWN AT THE FOOTER ON THE 2 STORY
 DETAIL ON D1.
  
 34) PROVIDE ADDITIONAL DETAILS FOR THE
 CIRCULAR STAIRS. SPECIFY THE WIDTH OF
 THE STAIRS, HANDRAILS 34"- 38" ABOVE THE
 LEADING EDGE OF TREADS PER FBC 1007.5,
 GUARDRAILS WITH INTERMEDIATE RAILS PER
 FBC 1015 AND SHOW COMPLIANCE WITH FBC
 1007.8.3 FOR MINIMUM TREAD DEPTHS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW