Plan Review Notes For Permit 03101960 |
Permit Number |
03101960 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-12-17 00:00:00 | *********** NOTE ************* | | | | 1)NOTE: PLEASE SEE THAT LOAD CALCULATION | | -S AND INFORMATION FAXED AND BROUGHT | | INTO OFFICE FROM EMPIRE ELEC FOR BLUE | | HAVEN POOLSARE STILL NOT CORRECT AS | | FOR ALL INFORMATION REQUESTED ON ORIG | | REVIEW. THREE SETS OF CALCS HAVE BEEN | | REVIEW. | | ELECTRICAL PERMIT HAS BEEN VOIDED AND | | POOL PERMIT IS BEING ISSUED. | | SEPARATE ELECTRICAL APPLICATION/FEES AND | | COMPLETE PLANS AND LOADS CALCULATIONS | | WILL BE REQ'D TO BE SUBMITTED AT A LATER | | DATE BEFORE ANY ELECTRICAL WORK ON POOL | | SHALL COMMENCE. | | PLEASE ALSO SUBMIT ALL MANF. SPECS ON | | ALL EQUIPMENT AT THAT TIME. | | ELEC PERMIT VOIDED PER JIM KILFEATHER | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|