Plan Review Notes
Plan Review Notes For Permit 03101794
Permit Number 03101794
Review Stop B
Sequence Number 9
Notes
Date Text
2005-01-10 00:00:00REVISION CHECKLIST:
  
 1-SHEET A4 AND SHEET A5 SPECIFICATIONS
 FOR ATTIC LIVE LOAD DO NOT MATCH.
 BESIDES AREAS TO HAVE STORAGE ARE
 REQUIRED TO BE DESIGNED FOR 30PSF LIVE
 LOAD AS REQUIRED BY TABLE 1604.1 FBC
 2001.
  
 2-TRUSS ENGINEER DID NOT FOLLOW
 ARCHITECT'S SPECIFICATIONS REQUIRING
 30PSF ATTIC LIVE LOAD DESIGN ON AREAS
 DESIGNATED TO BE FOR STORAGE.
  
 3-FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 SLIDING GLASS DOORS HAS NOT BEING
 RESUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.