Plan Review Notes For Permit 03101794 |
Permit Number |
03101794 |
|
Review Stop |
E |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2004-11-18 00:00:00 | ************ UNSAT *************** | | | | PLEASE SEE THAT REDLINED ITEMS FROM | | PREVIOUS REVIEWS HAVE NOT BEEN | | ADDRESSED. | | PLEASE ALSO SEE NEW COMMENTS FOR PLAN | | CHANGES. | | | | 1)NOTE: PLEASE SEE 250.24,250.6, THERE | | IS NO EQUIPMENT GROUNDING CONDUCTOR | | FROM | | METER TO FIRST MEANS OF DISCONNECT. | | | | 2)NOTE: PLEASE SEE PLANS STILL NOTE | | MAINS NEXT TO METER.?? | | | | 3)NOTE: PLEASE SEE GROUNDING ELECTRODE | | CONDUCTOR TO BE SIZED PER 250.66. | | ORIG PLANS CALLED FOR SMALLER SERVICE | | AND THIS WAS REDLINED ON PREVIOUS | | REVIEWS. TO BE SIZED PER 250.66 | | | | 4)NOTE: PLEASE SEE HAND DRAWN ITEMS MAY | | NOT BE DONE ON PLANS WHICH ARE SIGNED | | AND SEALED BY AN ARCH OR ENGINEER. | | FS 481.221 | | | | 5)NOTE: PLEASE SEE SD PLACEMENT, | | REQUIRES SD OUTSIDE MASTER BEDRM AND | | ALSO OUTSIDE GUEST SUITE. | | NFPA-72 8-1.4.1.6.2 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|