Plan Review Notes
Plan Review Notes For Permit 03101794
Permit Number 03101794
Review Stop E
Sequence Number 6
Notes
Date Text
2004-11-18 00:00:00************ UNSAT ***************
  
 PLEASE SEE THAT REDLINED ITEMS FROM
 PREVIOUS REVIEWS HAVE NOT BEEN
 ADDRESSED.
 PLEASE ALSO SEE NEW COMMENTS FOR PLAN
 CHANGES.
  
 1)NOTE: PLEASE SEE 250.24,250.6, THERE
 IS NO EQUIPMENT GROUNDING CONDUCTOR
 FROM
 METER TO FIRST MEANS OF DISCONNECT.
  
 2)NOTE: PLEASE SEE PLANS STILL NOTE
 MAINS NEXT TO METER.??
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66.
 ORIG PLANS CALLED FOR SMALLER SERVICE
 AND THIS WAS REDLINED ON PREVIOUS
 REVIEWS. TO BE SIZED PER 250.66
  
 4)NOTE: PLEASE SEE HAND DRAWN ITEMS MAY
 NOT BE DONE ON PLANS WHICH ARE SIGNED
 AND SEALED BY AN ARCH OR ENGINEER.
 FS 481.221
  
 5)NOTE: PLEASE SEE SD PLACEMENT,
 REQUIRES SD OUTSIDE MASTER BEDRM AND
 ALSO OUTSIDE GUEST SUITE.
 NFPA-72 8-1.4.1.6.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  