2004-02-04 00:00:00PLANS REVISED, DID NOT REVISE ORIG
 REDLINES.
 REDLINED PLANS FOR GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66 #2 MIN
 AND MISSING EQUIPMENT GROUNDING CONDUCT-
 ORS BETWEEN MAINS AND PANELS.