Plan Review Notes
Plan Review Notes For Permit 03101794
Permit Number 03101794
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-22 00:00:00********** NOTES REDLINED ************
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO PANELS
 PER 250.110, 250.24,250.122
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR FROM 250.66./ 310.15B6
  
 3)NOTE: PLEASE SEE 210.52 BEDROOM.
  
 ABOVE HAS BEEN REDLINED. IF REV'S ARE
 DONE, PLEASE MAKE ABOVE CORRECTIONS
 AND SUBMIT W/ REVISIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  