2004-01-07 00:00:00BUILDING REVIEW CHECKLIST:
 1-MISSING ONE DWG A1 & A2. ONLY ONE COPY
 OF REVISED A1 AND A2 DWG WAS SUBMITTED
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-ARCHITECT TO PROVIDE ALL INFORMATION
 LISTED ON SEC. 1606.1.7 FBC 2001.
 4-WHEN HAVING THE OPTION OF HAVING THE
 FIREPLACE, THEN ALL DETAILS & SPECS
 SHALL BE INCLUDED IN THE CONSTRUCTION
 DOCUMENTS. OTHERWISE, DELETE OPTION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-LIVING ROOM AREA: PROVIDE COMPLETE
 SECTION/DETAIL AT COLUMN SHOWING HOW
 ARE WINDOWS GOING TO BE ATTACHED.
 **NOTE: CHECK WINDOW PRODUCT APPROVAL
 FOR REQUIRED SUBSTRATE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 6-PLANS NEED TO SPECIFY SAFETY GLASS AT
 LIVING ROOM WINDOWS. SEC. 2405.2 FBC.
 7-PROVIDE FLORIDA PRODUCT APPROVAL FOR
 ENTRY DOOR WITH SIZE AS SHOWN ON PLAN.
 8-ROOF TILE FASTENING SPECIFIED IS NOT
 ADEQUATE. SEE PRODUCT APPROVAL FOR MIN
 REQUIRED SIZES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 9-RE-SUBMIT FLORIDA PRODUCT APPROVAL FOR
 A)"THERMA-TRU" ENTRY DOORS:*NEED SIZE AS
 SHOWN ON PLANS. **NO GOOD: PENDING FBC
 APPROVAL. ***NEED SWING OF DOOR AS
 SHOWN ON PLANS. ****SLIDING DOOR IS
 MISSING DRAWINGS AND IS PENDING FBC
 APPROVAL. NEED TO CHECK FOR SIZE AND
 SPECIFIC APPLICATION AS SHOWN ON PLANS
 B)GARAGE DOOR PRODUCT APPROVAL IS NOT
 APPROVED YET. IT'S APLIED FOR ONLY.
 C)IF USING FIXED WINDOWS BY "WINDSOR",
 THEN PROVIDE COMPLETE APPROVED DWGS &
 CHECK SIZES SHOWN ON PLANS.
 D)PGT PRODUCT APPROVAL PACKAGE: ONLY
 SUBMIT PRODUCT APPROVAL AND DRAWINGS
 FOR WINDOWS/DOORS, MULLIONS TO BE USED
 ON THIS PROJECT TO AVOID UNNECESSARY
 PAPERWORK.
 **NEED DRAWINGS FOR CASEMENT WINDOWS,
 WINDOW MULLIONS, FIXED WINDOWS (CHECK
 SIZES SHOWN ON PLANS)
  
 10-NEED FL. PRODUCT APPROVAL FOR FRENCH
 DOORS. CHECK SIZE AND SWING.
 11-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR FIREPLACE AND BBQ AS REQ'D BY
 SECTIONS 2806 AND 2808 FBC 2001.
 12-STORM SHUTTERS: A)PROVIDE 2 COPIES
 SIGNED,SEALED AS REQ'D BY ENGINEER.
 B)MEAN ROOF HEIGHT IS INCORRECT.
 C)ACCORDING TO INSTALLATION SCHEDULE
 SOME PANELS WILL ALLOW LESS THAN 2"
 EDGE DISTANCE. REVISE AS REQ'D.
 D)CLEARLY MARK ON ENGINEERED DRAWINGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE & SPACING TO BE USED ACCORDING TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND STRUC-
 TURE TO BE ATTACHED TO (CONCRETE BLOCK
 OR CONCRETE).
 E)NEED TO INDICATE EMERGENCY EGRESS AS
 REQ'D BY SECTION 1005.4.5. EGRESS TO
 BE ACCESSIBLE FOR EVERYBODY WITHOUT
 GOING THRU ROOMS THAT MAY BE LOCKED.
  
 13-CONTRACTOR SAID THAT HE WILL PROVIDE
 ADDITIONAL SOIL BORINGS AS REQ'D BY
 SOIL TEST REPORT.
 14-PROVIDE FLORIDA PRODUCT APPROVAL FOR
 TRUSS ANCHORS.
 15-REVISE ENERGY CALCULATIONS: A)UNDER
 ATTIC AREA IS INCORRECT. SEE SECTION
 604.1.A.1 CHAPTER 13 FBC 2001.
 16-REVISE TRUSS ANCHOR SCHEDULE:
 A)AVERAGE ULTIMATE TENSION CANN'T BE
 USED FOR DESIGN PURPOSES. SEE SIMPSON
 CONNECTOR HTT22. ALSO, CLARIFY WHAT
 ARE LATERAL FORCES F1 AND F2 TAKEN
 FROM. SEE CATALOGUE.
 **WHERE ARE LATERAL LOADS F1 & F2 TAKEN
 FROM?. PROVIDE ENGINEERING CALCS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 17-CONTRACTOR TO UPDATE WORKERS COMP.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ @ (561)805-6712.