2004-01-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-MISSING ONE DWG A1 & A2. ONLY ONE COPY |
| OF REVISED A1 AND A2 DWG WAS SUBMITTED |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-ARCHITECT TO PROVIDE ALL INFORMATION |
| LISTED ON SEC. 1606.1.7 FBC 2001. |
| 4-WHEN HAVING THE OPTION OF HAVING THE |
| FIREPLACE, THEN ALL DETAILS & SPECS |
| SHALL BE INCLUDED IN THE CONSTRUCTION |
| DOCUMENTS. OTHERWISE, DELETE OPTION. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 5-LIVING ROOM AREA: PROVIDE COMPLETE |
| SECTION/DETAIL AT COLUMN SHOWING HOW |
| ARE WINDOWS GOING TO BE ATTACHED. |
| **NOTE: CHECK WINDOW PRODUCT APPROVAL |
| FOR REQUIRED SUBSTRATE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 6-PLANS NEED TO SPECIFY SAFETY GLASS AT |
| LIVING ROOM WINDOWS. SEC. 2405.2 FBC. |
| 7-PROVIDE FLORIDA PRODUCT APPROVAL FOR |
| ENTRY DOOR WITH SIZE AS SHOWN ON PLAN. |
| 8-ROOF TILE FASTENING SPECIFIED IS NOT |
| ADEQUATE. SEE PRODUCT APPROVAL FOR MIN |
| REQUIRED SIZES. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 9-RE-SUBMIT FLORIDA PRODUCT APPROVAL FOR |
| A)"THERMA-TRU" ENTRY DOORS:*NEED SIZE AS |
| SHOWN ON PLANS. **NO GOOD: PENDING FBC |
| APPROVAL. ***NEED SWING OF DOOR AS |
| SHOWN ON PLANS. ****SLIDING DOOR IS |
| MISSING DRAWINGS AND IS PENDING FBC |
| APPROVAL. NEED TO CHECK FOR SIZE AND |
| SPECIFIC APPLICATION AS SHOWN ON PLANS |
| B)GARAGE DOOR PRODUCT APPROVAL IS NOT |
| APPROVED YET. IT'S APLIED FOR ONLY. |
| C)IF USING FIXED WINDOWS BY "WINDSOR", |
| THEN PROVIDE COMPLETE APPROVED DWGS & |
| CHECK SIZES SHOWN ON PLANS. |
| D)PGT PRODUCT APPROVAL PACKAGE: ONLY |
| SUBMIT PRODUCT APPROVAL AND DRAWINGS |
| FOR WINDOWS/DOORS, MULLIONS TO BE USED |
| ON THIS PROJECT TO AVOID UNNECESSARY |
| PAPERWORK. |
| **NEED DRAWINGS FOR CASEMENT WINDOWS, |
| WINDOW MULLIONS, FIXED WINDOWS (CHECK |
| SIZES SHOWN ON PLANS) |
| |
| 10-NEED FL. PRODUCT APPROVAL FOR FRENCH |
| DOORS. CHECK SIZE AND SWING. |
| 11-PROVIDE UL LISTING AND COMPLETE SPECS |
| FOR FIREPLACE AND BBQ AS REQ'D BY |
| SECTIONS 2806 AND 2808 FBC 2001. |
| 12-STORM SHUTTERS: A)PROVIDE 2 COPIES |
| SIGNED,SEALED AS REQ'D BY ENGINEER. |
| B)MEAN ROOF HEIGHT IS INCORRECT. |
| C)ACCORDING TO INSTALLATION SCHEDULE |
| SOME PANELS WILL ALLOW LESS THAN 2" |
| EDGE DISTANCE. REVISE AS REQ'D. |
| D)CLEARLY MARK ON ENGINEERED DRAWINGS |
| SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| TYPE & SPACING TO BE USED ACCORDING TO |
| THE DESIGN PRESSURES, EDGE DISTANCE, |
| PANEL SPAN, CONNECTION TYPE AND STRUC- |
| TURE TO BE ATTACHED TO (CONCRETE BLOCK |
| OR CONCRETE). |
| E)NEED TO INDICATE EMERGENCY EGRESS AS |
| REQ'D BY SECTION 1005.4.5. EGRESS TO |
| BE ACCESSIBLE FOR EVERYBODY WITHOUT |
| GOING THRU ROOMS THAT MAY BE LOCKED. |
| |
| 13-CONTRACTOR SAID THAT HE WILL PROVIDE |
| ADDITIONAL SOIL BORINGS AS REQ'D BY |
| SOIL TEST REPORT. |
| 14-PROVIDE FLORIDA PRODUCT APPROVAL FOR |
| TRUSS ANCHORS. |
| 15-REVISE ENERGY CALCULATIONS: A)UNDER |
| ATTIC AREA IS INCORRECT. SEE SECTION |
| 604.1.A.1 CHAPTER 13 FBC 2001. |
| 16-REVISE TRUSS ANCHOR SCHEDULE: |
| A)AVERAGE ULTIMATE TENSION CANN'T BE |
| USED FOR DESIGN PURPOSES. SEE SIMPSON |
| CONNECTOR HTT22. ALSO, CLARIFY WHAT |
| ARE LATERAL FORCES F1 AND F2 TAKEN |
| FROM. SEE CATALOGUE. |
| **WHERE ARE LATERAL LOADS F1 & F2 TAKEN |
| FROM?. PROVIDE ENGINEERING CALCS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 17-CONTRACTOR TO UPDATE WORKERS COMP. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |