2005-03-08 00:00:00 | CHECKLIST: |
| 1- SLIDING GLASS DOOR PRODUCT APPROVAL |
| COMMENTS FROM BILL STAPLES: |
| A) PROVIDE 2 COPIES OF F.B.C COVER SHEET |
| FILLED OUT. |
| |
| B) IF DOORS ARE GOING TO BE INSTALLED IN |
| 2 DIFFERENT LOCATIONS, THEN, APPLY FOR |
| LOCAL PRODUCT APPROVAL OR APPLY FOR SITE |
| SPECIFIC PRODUCT APPROVAL FOR EACH |
| HOUSE. |
| |
| C) WHO IS THE EVALUATION ENTITYIF |
| APLYING FOR LOCAL PRODUCT APPROVAL. |
| D) EVERY CHANGE DONE TO SIGN AND SEAL |
| DRAWINGS MUST BE INITILALIZED AND DATE |
| BY THE ENGINEER OF RECORD. |
| |
| E) INSPECTION FOR CODE COMPLIANCE IS |
| REQUIRED BY THE ENGINEER OF RECORD AFTER |
| ASSEMBLY IS INSTALLED. |
| |
| 2- REVISION COMMENTS: |
| A) PROVIDE COMPLETE UL LISTING AND SPECS |
| FOR INTERIOR FIREPLACE. SEC. 2806 FBC. |
| B) PROVIDE COMPLETE LISTING AND SPECS |
| FOR BBQ GRILL. SEC. 2808 FBC 2001. |
| ****NOTE: MAKE SURE THAT MANUFACTURER |
| SPECS ALLOW INSTALLATION OF GRILL IN THE |
| PORCH SINCE THEY ARE DESIGN TO BE |
| INSTALLED OUTDOORS. |
| |
| B) MASTER BATHROOM WINDOWS BY THE |
| WHIRPOOL NEED TO BE SPECIFIED AS SAFETY |
| GLASSS. SEC. 2405.2 FBC 2001. |
| |
| C) ATTIC SPACE WAS ORIGINALLY DESIGNED |
| FOR ATTIC STORAGE WITH 30PSF LIVE LOAD. |
| ATTIC WAS REVISED FOR NON-STORAGE. BUT |
| NEEDS TO BE DESIGNED FOR 10PSF ATTIC |
| LIVE LOAD AS REQUIRED BY TABLE 1604.1 |
| FBC 2001. NOW, THE PROBLEM IS THAT ROOF |
| TRUSSES WERE DESIGNED FOR 0 PSF ATTIC |
| LIVE LOAD. TRUSSES NEED TO COMPLY WITH |
| TABLE 1604.1 FBC 2001. |
| |
| D) BREAKFAST AREA WINDOW IS TO BE USED |
| FOR EMERGENCY EGRESS. STORM SHUTTERS |
| INSTALLATION SCHEDULE SHOWS WINDOW TO BE |
| SHUTTERED. PROVIDE CERTIFICATION THAT |
| THIS WINDOW WAS INSTALLED WITH MISSILE |
| IMPACT GLAZING IN ORDER TO COMPLY WITH |
| SEC. 1005.4.5 FBC 2001. |
| |
| E) OWES $80.00 REVISION FEES. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |