Plan Review Notes For Permit 03101794 |
Permit Number |
03101794 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-11-06 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE SHOW ROOM DESIGNATIONS | | ON PLANS. | | | | 2)NOTE: PLEASE SEE 210.52 FOR REQ'D | | RECEPT SPACING. | | | | 3)NOTE: PLEASE SEE 210.52D FOR REQ'D | | RECEPTS TO BE W/IN 3' OF SINKS. | | | | 4)NOTE: PLEASE SEC`S SHOWN AS 1/0'S. | | PLEASE SEE PER 310.16 OR MIN 310.15B6 | | FOR EACH 200A MAIN. | | | | 5)NOTE: PLEASE SEE MISSING GFI RECEPT | | FOR A/C COND UNITS. 210.63 | | | | 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT | | PROTECTED CIRCUITS PER 210.12 OF THE | | 2002 NEC. | | | | 7)NOTE: PLEASE SEE 250.66 FOR SIZING | | OF GR ELEC CONDUCTOR. SEEMS THE #4 AND | | #2 IS REVERSED. | | | | 8)NOTE: PLANS DO NOT SHOW MAIN DISC | | NEXT TO METER. | | | | | | PLEASE REMOVE OLD/VOIDED SHEETS AND | | INSERT NEW SHEETS INTO COMPLETE SETS FOR | | REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|