Plan Review Notes
Plan Review Notes For Permit 03101794
Permit Number 03101794
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-06 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ROOM DESIGNATIONS
 ON PLANS.
  
 2)NOTE: PLEASE SEE 210.52 FOR REQ'D
 RECEPT SPACING.
  
 3)NOTE: PLEASE SEE 210.52D FOR REQ'D
 RECEPTS TO BE W/IN 3' OF SINKS.
  
 4)NOTE: PLEASE SEC`S SHOWN AS 1/0'S.
 PLEASE SEE PER 310.16 OR MIN 310.15B6
 FOR EACH 200A MAIN.
  
 5)NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR A/C COND UNITS. 210.63
  
 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12 OF THE
 2002 NEC.
  
 7)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GR ELEC CONDUCTOR. SEEMS THE #4 AND
 #2 IS REVERSED.
  
 8)NOTE: PLANS DO NOT SHOW MAIN DISC
 NEXT TO METER.
  
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  