Plan Review Notes
Plan Review Notes For Permit 03101794
Permit Number 03101794
Review Stop B
Sequence Number 1
Notes
Date Text
2003-12-02 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-ARCHITECT TO PROVIDE COMPLETE INFO. ON
 PLANS AS REQ'D BY SEC. 1606.1.7 FBC.
 3-CLARIFY IF HAVING THE OPTION OF FIRE-
 PLACE OR NOT. IF SO, THEN PROVIDE
 COMPLETE SECTION/DETAILS AND SPECS FOR
 CHIMNEY AND UL LISTING AND SPECS.
 OTHERWISE REMOVE FIREPLACE AND CHIMNEY
 FROM PLANS ON ORIGINAL DWGS. DON'T
 CROSS OUT ORIGINAL PLANS.
 4-DESIGN CRITERIA TO INCLUDE 30PSF OR
 10PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001.
 5-FOOTING DETAILS AND WALL SECTIONS TO
 CLEARLY INDICATE THE 4"MIN. ELEVATION
 ABOVE GRADE AND THE 12" BELOW GRADE
 REQ'D BY SEC. 1804.1.7 CITY AMENDMENTS
 TO FBC AND SEC. 1804.1.3 FBC 2001.
 6-AS OF OCTOBER 1ST 2003 ALL PRODUCT
 APPROVAL FOR DOORS, WINDOWS AND
 STRUCTURAL COMPONENTS NEED TO HAVE THE
 FLORIDA PRODUCT APPROVAL, LOCAL
 PRODUCT APPROVAL OR SITE SPECIFIC. SEE
 CHAPTER 9B-72 DCA. PLEASE GO TO WWW.
 FLORIDABUILDING. ORG FOR MORE INFO.
 7-PROVIDE COMPLETE SECTION/DETAIL AND
 SPECS (TOP & BOTT.) FOR STEEL COLS. AT
 FAMILY RM WINDOW.
 **NOTE: INCLUDE ATTACHMENT OF WINDOW TO
 COL. SEE APPROVED PRODUCT APPROVAL.
 8-SPECIFY ATTIC ACCESS SIZE ON PLANS.
 SEE PLANS AND SEC. 2309.6 FBC 2001.
 9-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS & SEC. 2405.2 FBC 2001.
 10-PROVIDE COMPLETE SPECS FOR AHU DETAIL
 INCLUDE SIZE OF BOLTS AND CHAINS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 11-SPECIFY ROOF TILE FASTENING AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS FBC.
 12-PROVIDE COMPLETE DETAILS/SPECS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES. SEE ASTM C-926 & ASTM C-1063
 FOR STUCCO AND FASTENER SPECS.
 SEC. 2504.2 FBC 2001.
 13-INFORMATION ON SURVEY ISN'T COMPLETE.
 IS LOT BEING RECORDED?.SEE DESCRIPTION
 14-PROVIDE SOIL TEST REPORT W/ COMPLETE
 INFORMATION, SUCH AS SOIL PREPARATION
 AND SOIL BEARING CAPACITY. INFORMATION
 SUBMITTED ALSO RECOMMENDS ADDITIONAL
 BORINGS TO BE PERFORMED FOR FINAL
 GEOTECHNICAL RECOMMENDATIONS.
 15-STORM SHUTTERS INFO. IS INCOMPLETE.
 NEED FLORIDA PRODUCT APPROVAL. LOCAL
 APPROVAL OR SITE SPECIFIC DRAWINGS.
 ALSO, CLEARLY MARK ON DWGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING. SEC. 104.2.1.2 CITY AMENDMENT
 TO FBC 2001.
 16-ENERGY CALCULATIONS: A)REVISE UNDER
 ATTIC AREA. SEE SEC. 604.1.A.1 CHAPTER
 13 FBC 2001.
 B)CLARIFY HOW ARE INSULATION VALUES
 FOR CONCRETE SLAB, EXTERIOR CONCRETE
 WALL AND UNDER ATTIC GOING TO BE
 ACHIEVED. NOTE: ARCHITECTURAL PLANS &
 ENERGY CALCS NEED TO MATCH.
 17-SPECIFY FOOTING FOR ENTRY COLUMN. SEE
 FOUNDATION PLAN FOR COMMENTS & RETURN
 REVIEWED SET AFTER CORECTIONS ARE DONE
 TO CAD DWGS TO EXPEDITE REVIEW.
 18-SPECIFY MULLION/LINTEL ABOVE WINDOWS
 IN FAMILY ROOM. SEE BLDG SECTION A-A.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 19-SHEET A8: A)UPDATE GENERAL NOTES. SEE
 COMMENTS ON PLAN.
 B)COMPLETE/REVISE TYP. WALL SECTION.
 C)COMPLETE INFO. ON AHU DETAIL.
  
 20-ALL STRUCTURAL CONNECTORS NEED TO
 HAVE FLORIDA PRODUCT APPROVAL AS WELL.
 CHECK WITH USP OR SIMPSON FOR ANCHORS
 THAT HAVE SUCH APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CALL JULIO GOMEZ AT 805-6712.
  
 **PLEASE RETURN REVIEWED SET TO EXPEDITE
 THE REVIEW PROCESS.