2004-11-18 00:00:00*********** UNSAT *********
  
 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU#2.
  
 2)NOTE: PLEASE SEE 250.24, 250.6, NO
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 TO FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66 1/0
  
 4)NOTE: PLEASE SEE LOAD ON 1P20 BRKR FOR
 FRIG. THIS IS SHOWN ON ONE CIRCUIT.
 PLEASE NOTE: THIS IS THE SAME ON LOT
 #17, BUT WAS NOT TYPED IN NOTES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  