Plan Review Notes
Plan Review Notes For Permit 03101791
Permit Number 03101791
Review Stop E
Sequence Number 4
Notes
Date Text
2004-07-12 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PANELS AND
 RISER DIAGRAM. PANEL SHOWN AS 150A AND
 RISER SHOWS 200A'S.
  
 2)NOTE: PELASE CORRELATE LOADS , AWG AND
 OCP FOR A/C AHU'SETC.
 PLEASE SEE 424.3B MIN OCP TO BE 125%.
  
 3)NOTE: PLEASE SEE JACUZZI/WHIRLPOOL TUB
 LISTED ON PANEL SCHEDULE BUT NOT SHOWN
 ON PLANS.
  
 4)NOTE: PLEASE SEE GENERAL NOTES TO
 ELECTRICAL. PLEASE SEE NOTES #2 AND 4.
 PLEASE ADJUST NOTES.
 PLEASE SEE 210.12.
  
 5 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-07-08 00:00:00NO ELECTRICAL REVISION SUBMITTED.