2003-12-22 00:00:00********** NOTES REDLINED *************
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS.250.122
  
 2)NOTE: PLEASE SEE OCP FOR AHU/HEAT
 NEEDS TO BE SIZED PER 424.3B
  
 3)NOTE: GROUNDING ELECTRODE CONDCUTOR
 PER 250.66, MIN #2
  
 PLEASE SEE THAT THE ABOVE HAS BEEN
 REDLINED ON PLANS. PLEASE MAKE CORRECT-
 -IONS ALONG W/ ANY REV'S.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  