2004-01-08 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ENERGY CALCULATION FORM APPEARS
 TO CONTAIN ERRORS. THE CEILING AREA
 SHOULD BE MORE THAN THE FLOOR AREA DUE
 TO THE COFFERED CEILINGS IN SEVERAL OF
 THE ROOMS. SEE FBC CHAPTER 13 SECT.604.
 THE FORM LISTS THE R-VALUE OF THE FRAMED
 ADJACENT WALL AS R9. SHOULDN'T THIS BE
 R19 AT THE 2X6 WALL AND R11 AT THE 2X4
 PORTION OF THE WALL?
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 SOME OF THIS INFORMATION IS NOT ON THE
 PLANS.
  
 4) ON SHEET A5 THE D CONNECTION DETAIL
 IS INCORRECTLY SPECIFIED FOR THE GIRDER
 CONNECTION AT THE FRONT WALL OF BEDROOM.
 THERE IS NO COLUMN AT THIS LOCATION.
  
 5) PLEASE REVISE THE ANCHOR SCHEDULE ON
 A5. ROWS G,H & I HAVE INCORRECT VALUES
 IN THE F1 AND F2 COLUMNS FOR LATERAL
 LOADS. NO LATERAL LOADS ARE GIVEN IN THE
 CATALOG FOR THESE CONNECTORS. THE
 ULTIMATE UPLIFT VALUE IS LISTED FOR THE
 SIMPSON HTT22 CONNECTOR. USE THE DESIGN
 VALUE WHICH INCLUDES A SAFETY FACTOR.
  
 6) SPECIFY SAFETY GLASS FOR THE LIVING
 ROOM WINDOWS. SEE FBC 2405.2.1(4).
  
 7) INDICATE HOW THE WINDOWS/BUCKS ARE TO
 BE ATTACHED TO THE STEEL HEADER AND
 COLUMNS AT THE LIVING ROOM WINDOWS.
  
 8) SUBMIT MANUFACTURER'S SPECS. AND UL
 LISTING INFORMATION FOR OPTIONAL BBQ IF
 IT WILL BE INSTALLED.
  
 9) THE STORM PANEL KEY PLAN AND SCHEDULE
 CONTAINS SOME ERRORS. THE FRONT DOORS
 ARE SHOWN AS SOLID DOORS ON PLANS AND
 THEIR HEIGHT IS NINE FEET. THE GUEST
 ROOM DOOR IS IMPACT RESISTANT FOR EGRESS
 AND THE WRONG OPENING IS INDICATED ON
 THE KEY PLAN. OPENING #34 IS MARKED AS
 24 ON THE KEY PLAN. CHECK OPENING SIZES
 AND SPANS. CLEARLY MARK ON THE
 ENGINEERED DRAWINGS THE SPECIFIC TYPE OF
 MOUNTI, THE ANCHOR TYPE AND SPACING
 BASED ON DESIGN PRESSURES, EDGE DISTANCE
 PLANEL SPAN, ETC.
  
 10) PLEASE ATTACH THE COVER SHEETS FROM
 THE STATE PRODUCT APPROVALS TO THE
 APPROPRIATE DRAWINGS FOR THAT SPECIFIC
 ITEM (WINDOW, DOOR, ETC.). ONLY SUBMIT
 PRODUCT APPROVALS FOR ITEMS THAT WILL BE
 USED IN THIS PROJECT.
  
 11) SUBMIT INSTALLATION DRAWINGS FOR THE
 FIXED WINDOWS. ONLY THE STATE COVERSHEET
 WAS SUBMITTED.
  
 12) SUBMIT DRAWINGS FOR THE CASEMENT
 WINDOWS. ONLY STATE COVERSHEET SUBMITTED
  
 13) SUBMIT DRAWINGS FOR THE MULLIONS.
  
 14) THERE ARE NO STOREFRONT DOORS SHOWN
 ON THE PLANS. REMOVE THESE FROM THE
 SUBMITTAL OR SHOW THEIR LOCATION ON THE
 PLANS.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE AND DOUBLE FRENCH DOORS.
  
 16) DOUBLE HUNG AND HORIZONTAL SLIDING
 WINDOWS ARE NOT SHOWN ON THE PLANS.
 REMOVE THESE PRODUCT APP. FROM SUBMITTAL
  
 17) SUBMIT PRODUCT APPROVALS FOR BUTT
 GLASS WINDOW. SEE FBC 2406.2.
  
 18) SUBMIT PRODUCT APPROVALS FOR DOUBLE
 OUTSWING 9' HIGH ENTRY DOORS.
  
 19) CONTRACTOR'S WORKERS COMP. MUST BE
 UPDATED BEFORE PERMIT WILL BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714