2004-01-08 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE ENERGY CALCULATION FORM APPEARS |
| TO CONTAIN ERRORS. THE CEILING AREA |
| SHOULD BE MORE THAN THE FLOOR AREA DUE |
| TO THE COFFERED CEILINGS IN SEVERAL OF |
| THE ROOMS. SEE FBC CHAPTER 13 SECT.604. |
| THE FORM LISTS THE R-VALUE OF THE FRAMED |
| ADJACENT WALL AS R9. SHOULDN'T THIS BE |
| R19 AT THE 2X6 WALL AND R11 AT THE 2X4 |
| PORTION OF THE WALL? |
| |
| 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| SOME OF THIS INFORMATION IS NOT ON THE |
| PLANS. |
| |
| 4) ON SHEET A5 THE D CONNECTION DETAIL |
| IS INCORRECTLY SPECIFIED FOR THE GIRDER |
| CONNECTION AT THE FRONT WALL OF BEDROOM. |
| THERE IS NO COLUMN AT THIS LOCATION. |
| |
| 5) PLEASE REVISE THE ANCHOR SCHEDULE ON |
| A5. ROWS G,H & I HAVE INCORRECT VALUES |
| IN THE F1 AND F2 COLUMNS FOR LATERAL |
| LOADS. NO LATERAL LOADS ARE GIVEN IN THE |
| CATALOG FOR THESE CONNECTORS. THE |
| ULTIMATE UPLIFT VALUE IS LISTED FOR THE |
| SIMPSON HTT22 CONNECTOR. USE THE DESIGN |
| VALUE WHICH INCLUDES A SAFETY FACTOR. |
| |
| 6) SPECIFY SAFETY GLASS FOR THE LIVING |
| ROOM WINDOWS. SEE FBC 2405.2.1(4). |
| |
| 7) INDICATE HOW THE WINDOWS/BUCKS ARE TO |
| BE ATTACHED TO THE STEEL HEADER AND |
| COLUMNS AT THE LIVING ROOM WINDOWS. |
| |
| 8) SUBMIT MANUFACTURER'S SPECS. AND UL |
| LISTING INFORMATION FOR OPTIONAL BBQ IF |
| IT WILL BE INSTALLED. |
| |
| 9) THE STORM PANEL KEY PLAN AND SCHEDULE |
| CONTAINS SOME ERRORS. THE FRONT DOORS |
| ARE SHOWN AS SOLID DOORS ON PLANS AND |
| THEIR HEIGHT IS NINE FEET. THE GUEST |
| ROOM DOOR IS IMPACT RESISTANT FOR EGRESS |
| AND THE WRONG OPENING IS INDICATED ON |
| THE KEY PLAN. OPENING #34 IS MARKED AS |
| 24 ON THE KEY PLAN. CHECK OPENING SIZES |
| AND SPANS. CLEARLY MARK ON THE |
| ENGINEERED DRAWINGS THE SPECIFIC TYPE OF |
| MOUNTI, THE ANCHOR TYPE AND SPACING |
| BASED ON DESIGN PRESSURES, EDGE DISTANCE |
| PLANEL SPAN, ETC. |
| |
| 10) PLEASE ATTACH THE COVER SHEETS FROM |
| THE STATE PRODUCT APPROVALS TO THE |
| APPROPRIATE DRAWINGS FOR THAT SPECIFIC |
| ITEM (WINDOW, DOOR, ETC.). ONLY SUBMIT |
| PRODUCT APPROVALS FOR ITEMS THAT WILL BE |
| USED IN THIS PROJECT. |
| |
| 11) SUBMIT INSTALLATION DRAWINGS FOR THE |
| FIXED WINDOWS. ONLY THE STATE COVERSHEET |
| WAS SUBMITTED. |
| |
| 12) SUBMIT DRAWINGS FOR THE CASEMENT |
| WINDOWS. ONLY STATE COVERSHEET SUBMITTED |
| |
| 13) SUBMIT DRAWINGS FOR THE MULLIONS. |
| |
| 14) THERE ARE NO STOREFRONT DOORS SHOWN |
| ON THE PLANS. REMOVE THESE FROM THE |
| SUBMITTAL OR SHOW THEIR LOCATION ON THE |
| PLANS. |
| |
| 15) SUBMIT PRODUCT APPROVALS FOR THE |
| SINGLE AND DOUBLE FRENCH DOORS. |
| |
| 16) DOUBLE HUNG AND HORIZONTAL SLIDING |
| WINDOWS ARE NOT SHOWN ON THE PLANS. |
| REMOVE THESE PRODUCT APP. FROM SUBMITTAL |
| |
| 17) SUBMIT PRODUCT APPROVALS FOR BUTT |
| GLASS WINDOW. SEE FBC 2406.2. |
| |
| 18) SUBMIT PRODUCT APPROVALS FOR DOUBLE |
| OUTSWING 9' HIGH ENTRY DOORS. |
| |
| 19) CONTRACTOR'S WORKERS COMP. MUST BE |
| UPDATED BEFORE PERMIT WILL BE ISSUED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |