2003-11-06 00:00:00 | ************** UNSAT *************** |
| |
| 1)NOTE: PLEASE SIZE SEC'S PER 310.16 |
| OR 310.15B6 FOR A MIN. |
| SHOWS 1/0'SFOR 200A'S? |
| |
| 2)NOTE: PLEASE SEE THE GEC TO FOOTER |
| STEEL SHOULD BE SIZE PER 250.66. |
| THE #2 SHOWN SEEMS TO BE REVERSED WITH |
| THE # 4.. |
| |
| 3)NOTE: PLEASE SEE THAT WE ARE UNDER THE |
| 2002 NEC AND 210.12 HAS CHANGED FROM |
| WHAT IS NOTED ON PLANS FOR ARC FAULT. |
| PLEASE LIST THE REQ'D ARC FAULT PROTECT- |
| -ED CIRCUITS ON PANEL SCHEDULE. |
| 210.12 |
| |
| 4)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| SPACING, THERE ARE A FEW MISSING. |
| |
| 5)NOTE: PLEASE SEE 210.63 FOR REQ'D |
| GFI RECEPT FOR A/C COND UNITS. |
| |
| 6)NOTE: PLEASE SEE 210.52D FOR RECEPT |
| SPACING FROM SINKS/LAV. |
| |
| 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| ON PLANS FOR ALL ROOMS. |
| |
| 8)NOTE: PLEASE SEE MISSING SD FOR WHAT |
| APPEARS TO BE A BEDROOM/ADAPTABLE BEDRM |
| PER NFPA-72 8-1.4.2. SD IS ALSO REQ'D |
| TO BE INSIDE BEDROOM(MASTER?). |
| |
| 9)NOTE: PLEASE SEE PLANS, DOES NOT SHOW |
| MAIN DISCONNECT NEXT TO METER? |
| 215.5 |
| |
| 10)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| ED. 210.8.A6 |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. IF THERE ARE |
| ANY QUESTIONS, PLEASE CALL. |
| |