Plan Review Notes
Plan Review Notes For Permit 03101791
Permit Number 03101791
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-06 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SIZE SEC'S PER 310.16
 OR 310.15B6 FOR A MIN.
 SHOWS 1/0'SFOR 200A'S?
  
 2)NOTE: PLEASE SEE THE GEC TO FOOTER
 STEEL SHOULD BE SIZE PER 250.66.
 THE #2 SHOWN SEEMS TO BE REVERSED WITH
 THE # 4..
  
 3)NOTE: PLEASE SEE THAT WE ARE UNDER THE
 2002 NEC AND 210.12 HAS CHANGED FROM
 WHAT IS NOTED ON PLANS FOR ARC FAULT.
 PLEASE LIST THE REQ'D ARC FAULT PROTECT-
 -ED CIRCUITS ON PANEL SCHEDULE.
 210.12
  
 4)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING, THERE ARE A FEW MISSING.
  
 5)NOTE: PLEASE SEE 210.63 FOR REQ'D
 GFI RECEPT FOR A/C COND UNITS.
  
 6)NOTE: PLEASE SEE 210.52D FOR RECEPT
 SPACING FROM SINKS/LAV.
  
 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS FOR ALL ROOMS.
  
 8)NOTE: PLEASE SEE MISSING SD FOR WHAT
 APPEARS TO BE A BEDROOM/ADAPTABLE BEDRM
 PER NFPA-72 8-1.4.2. SD IS ALSO REQ'D
 TO BE INSIDE BEDROOM(MASTER?).
  
 9)NOTE: PLEASE SEE PLANS, DOES NOT SHOW
 MAIN DISCONNECT NEXT TO METER?
 215.5
  
 10)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. 210.8.A6
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]