Date |
Text |
2003-12-01 00:00:00 | UNSAT |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) ON SHEET A3 THE C8 COLUMN IS NOT |
| LISTED IN THE COLUMN SCHEDULE. |
| |
| 3) SAFETY GLAZING IS REQUIRED IN WINDOWS |
| THAT ARE WITHIN 3' HORIZONTALLY OF A TUB |
| OR SHOWER. SEE FBC 2405.2. SPECIFY ON |
| PLANS. |
| |
| 4) INSULATED OR SOLID CORE DOORS ARE |
| REQUIRED BETWEEN THE GARAGES AND THE |
| CONDITIONED SPACE PER FBC CHAPTER 13. |
| SPECIFY ON PLANS. |
| |
| 5) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| IN HER CLOSET. SEE FBC 2309.6. |
| |
| 6)SPECIFY THE ATTIC ACCESS FOR SERVICING |
| OF THE AHU IN ATTIC OF GOLF CART GARAGE. |
| SEE FBC MECHANICAL 306.3. CLARIFY THE |
| LOCATION OF THIS UNIT. THE ROOF FRAMING |
| PLAN INDICATES THAT IT IS HUNG FROM THE |
| TRUSSES AND NOT IN THE ATTIC. |
| |
| 7) SUBMIT MANUFACTURER'S SPECS. AND UL |
| LISTING INFORMATION FOR THE BBQ ON THE |
| LANAI. |
| |
| 8) THE ROOF FRAMING PLAN ON A5 SPECIFIES |
| DETAILS B,C & D ON A4. THESE DETAILS ARE |
| ON SHEET A5 AND ARE INCORRECTLY LABELED |
| AS A4. PLEASE CORRECT. |
| |
| 9) THE STEEL COLUMN CAPS HAVE THE WRONG |
| CONFIGURATIONS SPECIFIED AT SEVERAL |
| LOCATIONS. HANGERS ARE INDICATED AT STL. |
| COLUMNS AND CAPS ARE SPECIFIED WHERE |
| THERE ISN,T A COLUMN. SEE SHEET A5 AND |
| DETAILS ON A5. |
| |
| 10) PROVIDE DETAILS FOR THE 3"X 6" TUBE |
| STEEL COLUMN BASES AND CAPS. |
| |
| 11) SOME OF THE GIRDERS DO NOT HAVE A |
| CONNECTOR SPECIFIED. SEE THE NOTES ON |
| A5. |
| |
| 12) THE NOTE ON THE WALL SECTION ON A8 |
| EXCLUDES SOFFIT VENTS AT CROWN FACIA |
| AREAS. SPECIFY THAT ATTIC VENTS SHALL |
| PROVIDE A NET FREE VENT AREA WITH A |
| RATIO OF 1/150 OF CEILING AREA. SEE FBC |
| 2309.7. |
| |
| 13) PLEASE UPDATE THE REFERENCE TO THE |
| SBC 97 TO THE 2001 FBC ON A8. ALSO |
| UPDATE THE SPECIFIED HUGHES CONNECTOR TO |
| A CURRENT CONNECTOR. HUGHES IS NO LONGER |
| IN BUSINESS. |
| |
| 14) CORRECT THE R VALUES LISTED ON THE |
| ENERGY CALCULATION FORM. THE CEILING |
| INSULATION IS R30 ON THE PLANS. THE R |
| VALUE OF THE INSULATION AT THE CMU |
| EXTERIOR WALLS IS 4.2. THE ADJACENT |
| FRAME WALL SHOULD BE R-19 FOR 2X6 OR |
| R-11 FOR 2X4 WALLS. |
| |
| 15) CHANGE THE R VALUE OF THE INSULATION |
| AT THE ATTIC ACCESS DETAIL ON A9 TO |
| R-30 TO CORRESPOND WITH THE WALL SECTION |
| ON A8. |
| |
| 16) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. |
| |
| 17) SUBMIT ENGINEERING FOR BUTT GLASS |
| WINDOW PER FBC 2406.2. |
| |
| 18) SUBMIT PRODUCT APPROVALS FOR FIXED |
| GLASS, ARCHED FIXED GLASS AND CASEMENT |
| WINDOWS, STRUCTURAL MULLIONS, OUTSWING |
| ENTRY DOORS AND STORM PANELS. |
| |
| 19) SUBMIT THE APPROVED DRAWINGS FOR THE |
| OVERHEAD GARAGE DOORS. |
| |
| 20) PLEASE CLARIFY WHERE THE ALUMINUM |
| STOREFRONT DOORS WILL BE INSTALLED. |
| NOTE THE LIMITATION ON THE PRODUCT |
| APPROVAL FOR WATER INTRUSION WITHOUT AN |
| ADEQUATE OVERHANG. |
| |
| 21) PRODUCT APPROVALS FOR IMPACT AND |
| NON-IMPACT RESISTANT SH WINDOWS AND |
| STOREFRONT DOORS WERE SUBMITTED. PLEASE |
| CLARIFY. |
| |
| 22)FBC 1005.4.5 (GLITCH AMENDMENTS |
| JULY 1, 2003) REQUIRES AT LEAST ONE |
| MEANS OF ESCAPE FROM A DWELLING WHEN |
| SHUTTERED FOR IMPACT PROTECTION. THE |
| MEANS OF ESCAPE SHALL BE WITHIN THE |
| FIRST FLOOR OF THE DWELLING AND CAN NOT |
| BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| PART OF THE DWELLING SHALL HAVE ACCESS |
| TO IT WITHOUT HAVING TO PASS THROUGH A |
| LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| INDICATE HOW COMPLIANCE WILL BE |
| ACHIEVED AT THE OPTIONAL GUEST SUITE. |
| THE KEY PLAN INDICATES IMPACT GLASS FOR |
| EGRESS AT THE WRONG LOCATION. |
| |
| IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE |
| RETURN OLD PLANS WITH RESUBMITTAL. |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |