2003-11-06 00:00:00 | PLAN DENIED | | (1 RETURN AIR REQUIREMENTS TO COMPLY | | WITH THE F.B.C (M)2003 CHANGES.THE | | CHANGES WENT INTO EFFECT JULY 1 2003 | | 2) CAN NOT HAVE RETURN AIR IN LAUNDRY | | ROOM | | 3) REFER TO SECTION 307.2.3 AUXILLIARY | | DRAIN PANS.AUXILLIARY DRAIN PANS SHALL | | BE INSTALLED UNDER ALL COILS ON WHICH | | CONDENSATION WILL OCCUR. | | PLAN REVIEW BY HAROLD MOSER | | (561)805-6732 |
|