Plan Review Notes
Plan Review Notes For Permit 03101696
Permit Number 03101696
Review Stop B
Sequence Number 3
Notes
Date Text
2004-01-26 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-SHEET S-3: A)DIAPHRAGM SCHEDULE AND
 ROOF SHEATHING AND NAILING NOTE DON'T
 MATCH. REVISE/CLARIFY AS REQUIRED.
 B)CONNECTOR TC-5 @ MASONRY APPLICATION:
 SEE USP TECHNICAL BULLETIN AND REVISE
 SIZE OF SCREW TO ACHIEVE REQUIRED MIN.
 EMBEDMENT. ALSO, CLARIFY IF THIS
 CONNECTOR WAS REVISED/UPDATED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE STEEL STRESS
 TO BE INCREASED.
 C)CLARIFY WHY UPLIFT SHOWN ON TRUSS
 ANCHOR SCHEUDLE IS HIGHER THAN THE
 ONE PUBLISHED BY USP. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)ROOF TILE.
 B)8'X7' GARAGE DOOR THAT MEET THE DESIGN
 PRESSURES CALCULATED BY ARCHITECT.
 C)STRUCTURAL CONNECTORS.