2003-12-24 00:00:00BUILDING REVIEW CHECKLIST:
 1-LOAD SCHEDULE: ADD THE 30PSF/10PSF
 ATTIC LIVE LOAD AS REQUIRED BY TABLE
 1604.1 FBC 2001.
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS INCLUDING FLORIDA PRODUCT
 APPROVAL.
 3-REVISE ROOF SHEATHING AND NAILING NOTE
 AND DIAPHRAGM SCHEDULE ON SHEET S-3.
 SEE TABLE 2306.1 CITY AMENDMENTS TO
 FBC 20001 FOR REQUIRED NAILING SIZE &
 SPACING AT 25' MEAN ROOF HEIGHT.
 4-SHEET A-5: REVISE HANDRAIL HEIGHT TO
 COMPLY WITH SEC. 1007.5.1 FBC 2001.
 5-PROVIDE COMPLETE SOIL TEST REPORT WITH
 SOIL BEARING PREPARATION AND BEARING
 CAPACITY. SECTION 1804.2.2 OF CITY
 AMENDMENTS TO FBC 2001.
 6-PROVIDE FLORIDA PRODUCT APPROVALS OR
 SITE SPECIFIC ENGINEERING FOR ROOF
 TILE, ALL TYPES OF WINDOWS AND DOORS
 (SEE PLANS), WINDOW MULLIONS, TRUSS
 ANCHORS. VISIT WWW.FLORIDABUILDING.ORG
 FOR ALL THE INFORMATION REQUIRED TO BE
 SUBMITTED.
 7-SHEET S-3: REVISE CONNECTOR TC-5. THIS
 IS A WOOD TO WOOD CONNECTOR, WHILE,
 APPLICATION IS WOOD TRUSS TO MASONRY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-ARCHITECT TO PROVIDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED BY SECTION
 61G1-16.004 OF THE FLORIDA ADMINISTRA-
 TIVE CODE.
 9-ARCHITECT TO UPDATE SPECIFICATIONS ON
 SHEET C-1. SEE COMMENTS.
 10-SHEET A-1: CLARIFY NOTE #24. WHAT'S
 THE HEIGHT OF THE HANDRAIL?.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.