2003-11-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TOTHE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025.
 SEE SHEET E-2.
  
 2} PLEASE SEE NOTES ON PLANS REGARDING
 HOW THE SMOKE DETECTORS ARE FED.SHEET
 E-1 SHOWS THEM BEING FED FROM A KITCHEN
 OR BATHROOM LIGHT CIRCUIT.NOTE #14 ON
 E-2 SAYS THE SAME THING.PLEASE NOTE
 THAT NFPA-70 (NEC) 2002 EDITION
 REQUIRES THESE AND ALL "OUTLETS" (SEE
 DEFINITION IN NEC),BE PROTECTED BY ARC
 FAULT CIRCUIT INTERUPTERS. SEE210.12(B).
 PLEASE CHANGE THIS WORDING ON ALL
 FUTURE PLANS,ALL MODELS.THANKS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718