2003-11-19 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-LOAD SCHEDULE: ADD THE ATTIC LIVE LOAD |
| AS REQUIRED BY TABLE 1604.1 FBC 2001. |
| **NOTE: ADD 30PSF LIVE LOAD FOR ATTIC |
| WITH STORAGE AND 10PSF W/O STORAGE. |
| 2-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS: A)NEED FLORIDA PRODUCT |
| APPROVAL FOR LOCAL PRODUCT APPROVAL. |
| B)PROVIDE KEY PLAN AND COMPLETE INSTALLA |
| TION SCHEDULE. |
| C)CLEARLY MARK ON DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS AND ANCHOR TYPE & |
| SPACING. |
| 3-REVISE ROOF SHEATHING AND NAILING |
| NOTE AND DIAPHRAGM SCHEUDLE ON SHEET |
| S-3. SEE TABLE 2306.1 CITY AMENDMENTS |
| TO FBC 2001 FOR REQUIRED NAILING AT |
| MEAN ROOF HEIGHT OF 25' OR MORE. |
| 4-SHEET A-5: REVISE HANDRAIL HEIGHT TO |
| COMPLY WITH SEC. 1007.5.1 FBC 2001. |
| 5-PROVIDE COMPLETE SOIL TEST REPORT WITH |
| SOIL BEARING INFORMATION AND SOIL |
| PREPARATION. SECTION 1804.2.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 6-PROVIDE FLORIDA PRODUCT APPROVAL OR |
| LOCAL PRODUCT APPROVAL FOR ROOF TILE, |
| ALL TYPES OF DOORS AND WINDOWS, WINDOW |
| DOOR MULIIONS AS REQUIRED BY |
| FBC AS OF OCTOBER 1ST 2003. SEE COPY |
| OF FREQUENTLY ASKED QUESTION REGARDING |
| THIS NEW PROCESS. ALSO, VISIT WWW. |
| FLORIDABUILDING.ORG FOR MORE INFO. |
| |
| **NOTES: |
| * NEED PRODUCT APPROVAL FOR DOUBLE ENTRY |
| DOORS AS SHOWN ON PLANS. |
| * MAKE SURE ALL PROVIDED INFORMATION IS |
| NOT EXPIRED. |
| * ONLY SUBMIT INFORMATION FOR ITEMS THAT |
| APPLY TO THIS HOUSE TO REDUCE PAPER- |
| WORK AND UNNECESSARY REVIEWS. - |
| |
| 7-OWES $21.91 FOR UPDATED VALUATION. |
| SEE ATTACHED RECEIPT. |
| 8-SHEET S-3: ROOF FRAMING PLAN SPECIFIES |
| CONNECTOR TC-5 AND TC-6. BUT, THEY ARE |
| WOOD TO WOOD CONNECTORS. NEED MASONRY |
| CONNECTORS. REVISE AS REQUIRED. |
| 9-REVISE ENERGY CALCULATIONS: A)THIS IS |
| NOT LAKES OF LAGUNA. |
| B)THERE IS NOT ADJACENT WOOD WALL. SEE |
| PLANS AND REVISE AS REQUIRED. |
| C)PROVIDE TWO COPIES WITH ORIGINAL SEAL, |
| SIGNATURE AND DATE AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTES. |