Plan Review Notes For Permit 03101646 |
Permit Number |
03101646 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-12-02 00:00:00 | ******** NOTES ******** | | | | PLANS REDLINED. | | PLEASE SEE 700.12E FOR CIRCUITING OF | | EM/ EXT LTS. | | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% | | PER 215.3,230.42 ETC. | | | | PLEASE SEE THESE NOTES WERE FROM FIRST | | REVIEW. PLEASE SUBMIT PLANS WITH CORRECT | | -IONS BEFORE ROUGH ELECTRICAL INSPECTION | | IS CALLED IN. | | PLEASE SEE NOTES FROM FIRE REVIEW. | | | | PLEASE SEE NOTES ON FIRST REVIEW MENTION | | -S TO REMOVE ALL OLD/VOIDED SHEETS AND | | MAKE TWO COMPLETE STES FOR REVIEW AND | | STAMPING. PLEASE SEE THIS WAS NOT DONE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|