Plan Review Notes
Plan Review Notes For Permit 03101646
Permit Number 03101646
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-28 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
 BE SURE TO CIRCUIT EM/EXT LTS PER 700.12
 -E
  
 2)NOTE: PLEASE SHOW LOAD CALCULATION
 PER 220.3,220.10,220.11,220.13 ETC AND
 ALL CONTINUOUS LOADS PER 230.42,215.3
 LOAD CALC SHOWN IS FOR RESIDENTIAL.
  
 3)NOTE: PLANS REFERENCE 1999 NEC. WE
 ARE NOW UNDER THE 2002 NEC AS OF 7/1/03
  
 4)NOTE: PLEASE CLARIFY LOADS SHOWN FOR
 A/C AHU'S ??? NOT CLEAR WHICH ONE AND
 NOTE MENTIONS 1@ 10KW???
  
 5)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  