Plan Review Notes For Permit 03101646 |
Permit Number |
03101646 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-28 00:00:00 | ************** UNSAT ***************** | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | PLANS AND CORRELATE WITH SUBMITTED | | PANEL SCHEDULE. | | BE SURE TO CIRCUIT EM/EXT LTS PER 700.12 | | -E | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATION | | PER 220.3,220.10,220.11,220.13 ETC AND | | ALL CONTINUOUS LOADS PER 230.42,215.3 | | LOAD CALC SHOWN IS FOR RESIDENTIAL. | | | | 3)NOTE: PLANS REFERENCE 1999 NEC. WE | | ARE NOW UNDER THE 2002 NEC AS OF 7/1/03 | | | | 4)NOTE: PLEASE CLARIFY LOADS SHOWN FOR | | A/C AHU'S ??? NOT CLEAR WHICH ONE AND | | NOTE MENTIONS 1@ 10KW??? | | | | 5)NOTE: PLEASE CLARIFY NEW OR EXISTING | | SIGN CIRCUIT PER 600.5 | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | PLANS. | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | FOR REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|