Plan Review Notes For Permit 03101613 |
Permit Number |
03101613 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-30 00:00:00 | DENIED: | | 1.RETURN AIR REQUIRED FROM BEDROOM | | AREAS.PLEASE SIZE RETURN AIR ACCORDING | | TO THE ATTACHED SHEET. | | | | 2.PLEASE PROVIDE A COMPLETED FORM 600C | | IN ACCORDANCE WITH 2001 FBC CHAPTER 13 | | SUB-SECTION 600 METHOD C. | | | | 3.OVERFLOW PROTECTION REQUIRED AS PER | | 2001 FBC(M) 307.2.3, AUXILIARY DRAIN PAN | | REQUIRED. | | | | 4.CLARIFY "NO COOLING" IN THE FAMILY | | ROOM.IS THIS ROOM SEPARATED FROM THE | | REST OF THE HOUSE BY MEANS OF DOORS OR | | DOES IT HAVE INDEPENDENT COOLING? | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|