Plan Review Notes For Permit 03101544 |
Permit Number |
03101544 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-29 00:00:00 | DENIED: | | 1.PLAN DOES NOT INDICATE MAIN OR BRANC | | H DUCT SIZES. | | | | 2.RETURN AIR REQUIRED FROM BEDROOM | | AREAS.PLEASE SIZE RETURN AS PER | | REVISION TO THE 2001 FBC(M) 601.4, | | EFFECTIVE JUNE 30,2003: | | | | RETURN AIR JUMPER SHALL BE SIZED 1 1/2 | | TIMES THE CROSS SECTIONAL AREA OF THE | | SUPPLY DUCT FOR THE ROOM ITS SERVING | | WITH THE DOOR HAVING AN UNRESTRICTED 1" | | UNDERCUT. (ALL SUPPLY AIR TO THE ROOM | | SHALL BE CALCULATED) | | | | AIR TRANSFER GRILLES SHALL BE SIZED 50 | | SQ INCHES PER 100 CFM SUPPLY AIR. | | | | 3.EMERGENCY DRAIN PAN REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|