Plan Review Notes
Plan Review Notes For Permit 03101544
Permit Number 03101544
Review Stop M
Sequence Number 1
Notes
Date Text
2003-10-29 00:00:00DENIED:
 1.PLAN DOES NOT INDICATE MAIN OR BRANC
 H DUCT SIZES.
  
 2.RETURN AIR REQUIRED FROM BEDROOM
 AREAS.PLEASE SIZE RETURN AS PER
 REVISION TO THE 2001 FBC(M) 601.4,
 EFFECTIVE JUNE 30,2003:
  
 RETURN AIR JUMPER SHALL BE SIZED 1 1/2
 TIMES THE CROSS SECTIONAL AREA OF THE
 SUPPLY DUCT FOR THE ROOM ITS SERVING
 WITH THE DOOR HAVING AN UNRESTRICTED 1"
 UNDERCUT. (ALL SUPPLY AIR TO THE ROOM
 SHALL BE CALCULATED)
  
 AIR TRANSFER GRILLES SHALL BE SIZED 50
 SQ INCHES PER 100 CFM SUPPLY AIR.
  
 3.EMERGENCY DRAIN PAN REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.