2003-11-13 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG (HILL)
 BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)ENERGY CALCS REQUIRED, FBC13-101.2.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOTICE OF
 COMMENCEMENT WHICH WAS FILED ON 7/11 HAS
 EXPIRED AS WORK DID NOT COMMENCE WITHIN
 90 DAYS (FS713.13).
  
 4.)THE WALL SECTION DOES NOT SHOW
 CEILING OR WALL INSULATION.PLEASE NOTE
 THAT IF A FORM 600C ENERGY CALC IS
 SUBMITTED, MINIMUM UNDER ATTIC
 INSULATION REQUIRED IS R30, MINIMUM
 WALL INSULATION REQUIRED IS R5.REVISE
 WALL SECTION TO SHOW INSULATION.
  
 5.)SEPARATE PERMITS REQUIRED.
  
 6.)STATEWIDE OR LOCAL PRODUCT APPROVAL
 REQUIRED EFFECTIVE OCTOBER 1.FOR
 LISTED PRODUCTS (CAN SUBMIT THE APPROVAL
 ON THE WEBSITE) WWW.FLORIDABUILDING.ORG.
  
 PLEASE SUBMIT THE STATEWIDE PRODUCT
 APPROVAL WITH THE NOAS.
  
 FOR MORE INFORMATION ABOUT THE PROGRAM,
 SEE THE DCA WEBSITE AT
 WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/
 PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM