Plan Review Notes For Permit 03101411 |
Permit Number |
03101411 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-30 00:00:00 | ************ NOTES REDLINED/PROVISO***** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | WITH ALL EQUIPMENT BEING INSTALLED. | | RISER SHOWS ONLY ONE PUMP. PLANS SHOW | | 2 PUMPS AND BADU PUMP. | | PLEASE REVISE AND SUBMIT BEFORE FINAL. | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|