Plan Review Notes
Plan Review Notes For Permit 03101403
Permit Number 03101403
Review Stop P
Sequence Number 2
Notes
Date Text
2003-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW:
 SHT A-1 BREAK ROOM SINKS, ROOM 105 & 203
 SHALL BE ACCESSIBLE PER SECTION 11-4.24.
 SUBMIT A DETAIL SHOWING HEIGHT 11-4.24.2
 DEPTH 11-4.24.4, CLEAR FLOOR SPACE 11-4.
 24.5, AND FAUCETS 11-4.24.7. NO DETAIL
 WAS FOUND AS REQUESTED.
 2) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B) DESIGN PROFESSIONAL
 DOCUMENTS.
  