Plan Review Notes
Plan Review Notes For Permit 03101403
Permit Number 03101403
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-11-13 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM INSTALLATION.
  
 2) FIRE ALARM CIRCUITS SHALL BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE. AS OF
 AUGUST 1, 2003, ALL FIRE ALARM SYSTEMS
 THAT SUPERVISE FIRE SPRINKLERS SHALL
 BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 3) CENTRAL FIRE SPRINKLERS ARE CALLED
 OUT FOR USE. PLEASE VERIFY AT
 WWW.SPRINKLERREPLACEMENT.COM THAT
 THESE HEADS ARE NOT ON ANY RECALL LIST.
  
 4) A KNOX-BOX WILL BE REQUIRED.
  
 5) FOAM COLUMNS STILL SHOWN ON PLANS
 BUT PLAN REVIEW COMMENTS INDICATES
 THAT FOAM COLUMNS ARE NOT GOING TO
 BE USED. THIS ISSUE WILL BE CONSIDERED
 CLOSED BASED ON THE INFORMATION
 PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910