Plan Review Notes For Permit 03101403 |
Permit Number |
03101403 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-11-13 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM INSTALLATION. | | | | 2) FIRE ALARM CIRCUITS SHALL BE CLASS A, | | STYLE D OR FULLY ADDRESSABLE. AS OF | | AUGUST 1, 2003, ALL FIRE ALARM SYSTEMS | | THAT SUPERVISE FIRE SPRINKLERS SHALL | | BE UL LISTED FOR CENTRAL STATION | | SERVICE. | | | | 3) CENTRAL FIRE SPRINKLERS ARE CALLED | | OUT FOR USE. PLEASE VERIFY AT | | WWW.SPRINKLERREPLACEMENT.COM THAT | | THESE HEADS ARE NOT ON ANY RECALL LIST. | | | | 4) A KNOX-BOX WILL BE REQUIRED. | | | | 5) FOAM COLUMNS STILL SHOWN ON PLANS | | BUT PLAN REVIEW COMMENTS INDICATES | | THAT FOAM COLUMNS ARE NOT GOING TO | | BE USED. THIS ISSUE WILL BE CONSIDERED | | CLOSED BASED ON THE INFORMATION | | PROVIDED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|