Plan Review Notes
Plan Review Notes For Permit 03101403
Permit Number 03101403
Review Stop M
Sequence Number 1
Notes
Date Text
2003-10-30 00:00:00DENIED:
 SECOND FLOOR EAST STAIRWELL INDICATES
 DUCT RUNNING THROUGH THE STAIRWELL.AS
 PER 2001 FBC 1006.1.3.1 THE ONLY DUCT
 WORK ALLOWED IN A STAIRWELL IS FOR THE
 PURPOSE OF STAIRWELL PRESSURIZATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.